SECTION 2 - OPTIVIEW OPERATION
FORM 160.10-O1
ISSUE DATE: 4/27/2018
2
Condenser Pressure
This display indicates the refrigerant pressure in the
condenser.
Condenser Saturation Temperature
This display indicates the saturation temperature in the
condenser.
Oil Sump Temperature
This displays the temperature of the oil in the sump.
Oil Pressure
This display indicates the pressure differential between
the high side oil pressure transducer (output of oil
filter) and the low side oil pressure transducer (com-
pressor housing). The displayed value includes offset
pressure derived from auto-zeroing during the system
prelube. If either of the transducers used to calculate
this differential are out of range, the display field will
show XX.X.
% Full Load Amps
This displays the percentage of full load amps utilized
by the system.
Current Limit
This display indicates the current limit value in use.
This value could come from a 0-20mA, 4-20mA,
0-10VDC or 2-10VDC input in analog remote mode,
PWM signal in digital remote mode, MicroGateway
interface in ISN (Integrated Systems Network) mode,
or a locally programmed value.
PROGRAMMABLE
None
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.