APPENDIX B - PROGRAMMABLE SETPOINT VALUES
FORM 160.10-O1
ISSUE DATE: 4/27/2018
B
(MOD “B”) SOLID STATE STARTER SCREEN
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Motor Current Limit
Operator
30 %
100 %
100 %
Pulldown Demand Limit
Operator
30 %
100 %
100 %
Pulldown Demand Time
Operator
0 Min
255 Min
0 Min
Full Load Amps
Service
35 Amps
1050 Amps
35 Amps
Voltage Range
Service
Disabled, 200-208, 220-240, 380,
400, 415, 440-480, 550 – 600
Disabled
Starting Current
Service
310 Amps
3300 Amps
310 Amps
Open SCR
Service
Disabled
Enabled
Disabled
Shorted SCR
Service
Disabled
Enabled
Enabled
VARIABLE SPEED DRIVE SCREEN
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Motor Current Limit
Operator
30 %
100 %
100 %
Pulldown Demand Limit
Operator
30 %
100 %
100 %
Pulldown Demand Time
Operator
0 Min
255 Min
0 Min
Filter Inhibit
Service
Disabled
Enabled
Disabled
VARIABLE SPEED DRIVE DETAILS SCREEN (VARIABLE SPEED DRIVE SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Motor Current Limit
Operator
30 %
100 %
100 %
Pulldown Demand Limit
Operator
30 %
100 %
100 %
Pulldown Demand Time
Operator
0 Min
255 Min
0 Min
ADAPTIVE CAPACITY CONTROL DETAILS SCREEN (VARIABLE SPEED DRIVE SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Motor Current Limit
Service
30 %
100 %
100 %
Pulldown Demand Limit
Service
30 %
100 %
100 %
Pulldown Demand Time
Service
0 Min
255 Min
0 Min
Stability Limit
Service
1000
7000
4500
Surge Margin Adjust
Service
0.0 Hz
25.0 Hz
0.0 Hz
ACC Auto Map Print
Service
Disabled
Enabled
Disabled
HARMONIC FILTER (VARIABLE SPEED DRIVE SUBSCREEN)
SETPOINT
ACCESS
LEVEL
MINIMUM
VALUE
MAXIMUM
VALUE
DEFAULT
Local Motor Current Limit
Operator
30 %
100 %
100 %
Pulldown Demand Limit
Operator
30 %
100 %
100 %
Pulldown Demand Time
Operator
0 Min
255 Min
0 Min
TABLE 13 -
PROGRAMMABLE SETPOINT VALUES (CONT’D)