SECTION 2 - OPTIVIEW OPERATION
FORM 160.10-O1
ISSUE DATE: 4/27/2018
2
Exception Start/Stop Times
Access Level Required: OPERATOR
Exceptions allow the user may specify a non-standard
start and stop time for any day of the week, up to six
weeks in advance. As each week goes by, a new week-
ly schedule will automatically be created using the ex-
ception day(s) in combination with the standard week
schedule.
Schedule (Enabled / Disabled)
Access Level Required: OPERATOR
Allows the user to enable or disable the schedule fea-
ture, which controls scheduled starting and stopping of
the chiller. When the schedule is disabled, the chiller
must be manually started and stopped.
Repeat Sunday Schedule
Access Level Required: OPERATOR
Duplicates the schedule defined for Sunday to the re-
mainder of the standard, non-exception days for the
present week.
Reset All Exception Days
Access Level Required: OPERATOR
Deletes all programming for exception days within the
six week schedule.
Select
Access Level Required: OPERATOR
Places a selection box around a start time for a given
day. Use ◄, ►, ▲ or ▼ cursor arrows to move the box
and highlight the desired day or start/stop selection.
Access Level Required: VIEW
This function generates a “Schedule” print report.
NAVIGATION
Home
Access Level Required: VIEW
Returns the display to the Home screen.
Setup
Access Level Required: VIEW
Returns the display to the Setup screen.