JOHNSON CONTROLS
129
SECTION 4 - PRINTERS
FORM 160.10-O1
ISSUE DATE: 4/27/2018
4
YORK SETPOINTS
CHILLER ID 0
(c) 1997 – 2004 YORK INTERNATIONAL CORPORATION
Mon 22 Nov 2004 8:48:27 AM
Software Versions
-----------------------------------------------------
Controls
= C.MLM.08.01
BIOS
= C.MLM.00.03
Kernel
= 0.18
GUI
= 0.33
SIO
= 0.22
GPIC
= 0.04
Ext I/O
= 0110112091996
VSD
[Not displayed if Motor Type is not VSD]
= C.VSD.00.00
SSS [
Not displayed if Motor Type is not Mod B SSS]
= C.SSS.01.01
System Information
-----------------------------------------------------
System Language
= English
Data Display Mode
= English
Control Source
= Local
Remote Analog Input Range
= 0–10 Volts
Clock
= Enabled
Jumper Settings
-----------------------------------------------------
Oil Pump Type
= Standard
Coastdown
= Standard
Chilled Liquid Pump Operation
= Standard
Refrigerant Selection
= R123
Anti-Recycle
= Enabled
Power Failure Restart
= Auto
Liquid Type
= Water
Motor Type
= Fixed Speed
Printer Setup
-----------------------------------------------------
Automatic Printer Logging
= Disabled
Log Start Time
= 12:00 am
Output Interval
= 60 Min
Printer Type
= Okidata
Baud
= 9600 Baud
Data Bits
= 8 Bits
Parity
= None
Stop Bits
= 1 Bit
COM 2 Setup
-----------------------------------------------------
Baud
= 19200 Baud
Data Bits
= 8 Bits
Parity
= Odd
Stop Bits
= 1 Bit
Evaporator
-----------------------------------------------------
Leaving Chilled Local Setpoint
= 45.0 ºF
Leaving Chilled ISN Setpoint
= 45.0 ºF
Leaving Chilled Modem Setpoint
= 45.0 ºF
Leaving Chilled Analog Setpoint
= 45.0 ºF
Leaving Chilled Digital Setpoint
= 45.0 ºF
Remote Range
= 10.0 ºF
Sensitivity
= 100%
FIGURE 52 -
SAMPLE PRINTOUT (SETPOINTS)
Restart Offset
= 0.0 ºF
Restart Setpoint
= 45.0 ºF
Shutdown Offset
= 4.0 ºF
Shutdown Setpoint
= 41.0 ºF
Brine Low Evaporator Cutout
= 12.5 Psig
Smart Freeze
= Off
Refrigerant
= Enabled
Condenser
-----------------------------------------------------
High Pressure Warning Threshold
= 28.8 Psig
Drop Leg
= Enabled
Oil Sump
-----------------------------------------------------
Manual Pump
= Disabled
Low Pressure Limit
= 15.0 PSID
Prelube Time
= 30 Sec
Coastdown Time
= 150 Sec
Purge Control
-----------------------------------------------------
High Efficiency
= Off
Maximum Purge / Hour
= 20
[Following section not displayed if Hot Gas Bypass is not enabled]
Hot Gas
-----------------------------------------------------
Hot Gas
= Enabled
Hold Period
= 30 Min
Close Percentage
= 5 %
[Following section not displayed if Level Control is not enabled]
Refrigerant Level Control
-----------------------------------------------------
Level Control
= On
Setpoint
= 50 %
Period
= 3.5 Sec
Proportion Limit Open
= 15 %
Proportion Limit Close
= 45 %
Rate Limit Open
= 10 %
Rate Limit Close
= 10 %
[Not displayed if Motor Type is not EM]
Electro-Mechanical Starter
-----------------------------------------------------
Local Motor Current Limit
= 100 %
Remote ISN Current Limit
= 100 %
Remote Analog Current Limit
= 100 %
Remote Digital Current Limit
= 100 %
Remote Modem Current Limit
= 100 %
Pulldown Demand Limit
= 100 %
Pulldown Demand Time
= 0 Min
FIGURE 52 -
SAMPLE PRINTOUT (SETPOINTS)
(CONT’D)
Summary of Contents for YORK OPTIVIEW CONTROL CENTER
Page 12: ...JOHNSON CONTROLS 12 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 118: ...JOHNSON CONTROLS 118 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...
Page 140: ...JOHNSON CONTROLS 140 FORM 160 10 O1 ISSUE DATE 4 27 2018 THIS PAGE INTENTIONALLY LEFT BLANK...