JOHNSON CONTROLS
124
FORM 160.10-O1
ISSUE DATE: 4/27/2018
SECTION 4 - PRINTERS
[Skip the following section if Liquid Level is not enabled]
Refrigerant Level Control
-----------------------------------------------------
Refrigerant Level Position
= 35 %
Purge Control
-----------------------------------------------------
Pressure
= 30.1 PSIA
Exhaust Count
= 0
Exhaust Window
= 0 Min
[Skip the following section if Motor Type is not EM]
Electro-Mechanical Starter
-----------------------------------------------------
Motor Run
= On
% Full Load Amps
= 94 %
[Skip the following section if Motor Type is not Mod B SSS]
Liquid-Cooled Solid State Starter
-----------------------------------------------------
Starter Model
= 26L
Motor Run
= On
% Full Load Amps
= 95 %
kW Hours
= 20723 kWH
Input Power
= 8225 kW
Phase A Voltage
= 422 V
Phase B Voltage
= 449 V
Phase C Voltage
= 449 V
Phase A Current
= 253 A
Phase B Current
= 257 A
Phase C Current
= 262 A
Phase A Temperature
= 109 ºF
Phase B Temperature
= 109 ºF
Phase C Temperature
= 110 ºF
[Skip the following section if Motor Type is not VSD]
Variable Speed Drive
-----------------------------------------------------
Motor Run
= On
% Full Load Amps
= 94 %
Pre-Rotation Vanes Position
= 75 %
Full Load Amps
= 402 A
Precharge Relay Output
= Off
Trigger SCR Output
= On
Water Pump Output
= On
kW Hours
= 14528 kWH
Input Power
= 150 kW
Output Frequency
= 60 Hz
Output Voltage
= 800 V
DC Bus Voltage
= 600 V
DC Inverter Link Current
= 300 A
Phase A Output Current
= 195 A
Phase B Output Current
= 198 A
Phase C Output Current
= 193 A
Internal Ambient Temperature
= 88 ºF
Converter Heatsink Temperature
= 102 ºF
Phase A Heatsink Temperature [If TMIII VSD] = 93 ºF
Phase B Heatsink Temperature [If TMIII VSD] = 99 ºF
Phase C Heatsink Temperature [If TMIII VSD] = 97 ºF
Baseplate Temperature [If VyperDrive VSD] = 106 ºF
FIGURE 44 -
SAMPLE PRINTOUT (STATUS) (CONT’D)
[Skip the following section if Motor Type is not VSD or Filter is
not present]
Harmonic Filter Data
----------------------------------------------------
Precharge Contactor
= Off
Supply Contactor
= On
Operating Mode
= Running
Phase Rotation
= ABC
Total Supply kVA
= 148 kVA
Total Power Factor
= 0.97
DC Bus Voltage
= 608 V
Heatsink Temperature [If TMIII VSD]
= 102 ºF
Baseplate Temperature [If VyperDrive VSD] = 102 ºF
Voltage Peak N-L1
= 200 V
Voltage Peak N-L2
= 200 V
Voltage Peak N-L3
= 200 V
L1-L2 RMS Voltage
= 215 V
L2-L3 RMS Voltage
= 215 V
L3-L1 RMS Voltage
= 215 V
L1 RMS Filter Current
= 150 A
L2 RMS Filter Current
= 150 A
L3 RMS Filter Current
= 150 A
L1 RMS Supply Current
= 152 A
L2 RMS Supply Current
= 152 A
L3 RMS Supply Current
= 152 A
L1 Voltage Total Harmonic Distortion
= 1.5 %
L2 Voltage Total Harmonic Distortion
= 1.2 %
L3 Voltage Total Harmonic Distortion
= 1.1 %
L1 Supply Current Total Demand Distortion = 2.6 %
L2 Supply Current Total Demand Distortion = 2.3 %
L3 Supply Current Total Demand Distortion = 2.8 %
FIGURE 44 -
SAMPLE PRINTOUT (STATUS) (CONT’D)
Motor Winding Temperature
-----------------------------------------------------
A1
= 193.3 ºF
B1
= 192.5
ºF
B2
= 193.1
ºF
Bearing Temperature
-----------------------------------------------------
Sensor 1
= 128.3
ºF
Sensor 2
= 129.5
ºF
FIGURE 44 -
SAMPLE PRINTOUT (STATUS) (CONT’D)