QUANTUM™ LX COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.020-CS (APRIL 13)
Page 89
Frick®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data
Units
7930
N109:30
47931
R/W
High Entering Process Temperature Shutdown
Temperature
7931
N109:31
47932
R/W
High Entering Process Temperature Warning
7932
N109:32
47933
R/W
High Entering Process Temperature Shutdown Delay
Seconds
7933
N109:33
47934
R/W
High Entering Process Temperature Warning Delay
7934
N109:34
47935
R/W
Low Entering Process Temperature Shutdown
Temperature
7935
N109:35
47936
R/W
Low Entering Process Temperature Warning
7936
N109:36
47937
R/W
Low Entering Process Temperature Shutdown Delay
Seconds
7937
N109:37
47938
R/W
Low Entering Process Temperature Warning Delay
8000
N110:00
48001
R/W
PID 1 Setpoint
Temperature
8001
N110:01
48002
R/W
PID 1 Deadband
None
8002
N110:02
48003
R/W
PID 1 Proportional Band
Temp. (Magni-
tude)
8003
N110:03
48004
R/W
PID 1 Integral Gain
Real
8004
N110:04
48005
R/W
PID 1 Derivative Gain
8005
N110:05
48006
R/W
PID 1 High Limit
Percent (%)
8006
N110:06
48007
R/W
PID 1 Low Limit
8007
N110:07
48008
R/W
PID 1 When Running Off Value
8008
N110:08
48009
R/W
PID 2 Setpoint
None
8009
N110:09
48010
R/W
PID 2 Deadband
8010
N110:10
48011
R/W
PID 2 Proportional Band
8011
N110:11
48012
R/W
PID 2 Integral Gain
Real
8012
N110:12
48013
R/W
PID 2 Derivative Gain
8013
N110:13
48014
R/W
PID 2 High Limit
Percent (%)
8014
N110:14
48015
R/W
PID 2 Low Limit
8015
N110:15
48016
R/W
PID 2 When Running Off Value
8016
N110:16
48017
R/W
PID 3 Setpoint
None
8017
N110:17
48018
R/W
PID 3 Deadband
8018
N110:18
48019
R/W
PID 3 Proportional Band
8019
N110:19
48020
R/W
PID 3 Integral Gain
Real
8020
N110:20
48021
R/W
PID 3 Derivative Gain
8021
N110:21
48022
R/W
PID 3 High Limit
Percent (%)
8022
N110:22
48023
R/W
PID 3 Low Limit
8023
N110:23
48024
R/W
PID 3 When Running Off Value
8024
N110:24
48025
R/W
PID 4 Setpoint
None
8025
N110:25
48026
R/W
PID 4 Deadband
8026
N110:26
48027
R/W
PID 4 Proportional Band
8027
N110:27
48028
R/W
PID 4 Integral Gain
Real
8028
N110:28
48029
R/W
PID 4 Derivative Gain
8029
N110:29
48030
R/W
PID 4 High Limit
Percent (%)
8030
N110:30
48031
R/W
PID 4 Low Limit
8031
N110:31
48032
R/W
PID 4 When Running Off Value
SETPOINT VALUES (Continued):
Summary of Contents for Frick QUANTUM LX
Page 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 12 NOTES ...
Page 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 34 NOTES ...
Page 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 44 NOTES ...
Page 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 60 NOTES ...
Page 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 102 NOTES ...
Page 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 108 NOTES ...
Page 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 116 NOTES ...
Page 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 139 ...