QUANTUM™ LX COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.020-CS (APRIL 13)
Page 23
QUERY SETPOINTS DATA:
#IDQ1
Command structure:
Command
Description
#
Start command sequence
ID
Compressor
(ID)
code (01, 14, etc.)
Q1
(Q)
uery Setpoints command
Returned Answer:
Character
Position
#
Byte(s)
Setpoint (Name/Comment)
1
1
Always 0
2, 3, 4, 5
4
Capacity Control Setpoint, 3
chars followed by g or h
14, 15
2
Prop band
16, 17
2
Dead band
18, 19
2
Cycle time
20, 21, 22, 23
4
Future
24, 25, 26, 27
4
Future
28, 29, 30, 31
4
Future
32, 33
2
Future
34, 35
2
Future
36, 37
2
Future
38, 39, 40, 41
4
High Discharge Pressure Shut-
down
42, 43, 44, 45
4
High Discharge Pressure Warn-
ing
46
1
ID (tenths position byte)
47
1
ID (ones position byte)
48
1
ID Checksum of all data (pos. 1
to 47)
49
1
CR code 13
50
1
LF code 10
51
1
0 null terminator char.
QUERY SETPOINTS DATA:
#IDQ2
Command structure:
Command
Description
#
Start command sequence
ID
Compressor
(ID)
code (01, 14, etc.)
Q2
(Q)
uery Setpoints command
Returned Answer:
Character
Position
# Byte(s)
Setpoint (Name/Comment)
1, 2, 3
3
Future
4, 5, 6
3
Future
7, 8, 9
3
MLC amps stop load
10, 11, 12
3
MLC amps force unload
13, 14, 15
3
CT factor
16, 17
2
Recycle delay (setpoint,
not time left)
18
1
Aux 1
0 = Warning
1 = Shutdown
19
1
Aux 1
0 = NO
1 = NC
20
1
Aux 2
0 = Warning
1 = Shutdown
21
1
Aux 2
0 = NO
1 = NC
22
1
Future
23, 24
2
Future
25
1
Future
26
1
Future
27, 28
2
Future
29
1
Future
30
1
ID (tenths position byte)
31
1
ID (ones position byte)
32
1
ID Checksum of all data
(pos. 1 to 47)
33
1
CR code 13
34
1
LF code 10
35
1
0 null terminator char.
Summary of Contents for Frick QUANTUM LX
Page 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 12 NOTES ...
Page 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 34 NOTES ...
Page 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 44 NOTES ...
Page 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 60 NOTES ...
Page 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 102 NOTES ...
Page 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 108 NOTES ...
Page 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 116 NOTES ...
Page 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 139 ...