Test each individual cable run with an
approved CAT5 E cable tester. A TON-
ING alone test is NOT acceptable.
• Use rubber grommets anywhere that
the cable enters through a hole in a
metal panel.
• ALWAYS obey local, national and
fi
re
building codes.
Don’t:
• Don’t install cable taut, cables must
always have some “play” or slack in
them.
•
Don’t over-tighten cable ties.
•
Don’t splice a cable. If a break occurs,
or the length is not long enough (under
300 feet), replace the entire run with an
intact length.
•
Don’t tie cables to electrical conduits.
•
Don’t strip more than one inch from the
end of each cable when installing end
connectors.
•
Don’t sharply bend or kink the cable.
•
Don’t mix 568A and 568B wiring at the
same installation. 568B is the most
common wiring.
•
Don’t use excessive force when pulling
cable.
RJ-45 CONNECTORS
Ethernet network cables require the use of in-
dustry standard RJ-45 plugs as shown below, for
the termination of all cables:
Typical RJ-45 Connector
THE HUB
A Hub is a common connection point for devices
in a network. Hubs are commonly used to con-
nect segments of a LAN (Local Area Network).
They also contain multiple ports. When a data
packet arrives at one port, it is copied to the
other ports so that all segments of the LAN can
see all packets.
THE SWITCH
Network Switches look nearly identical to hubs,
but a switch generally contains more intelligence
than a hub. Unlike hubs, network switches are
capable of inspecting the data packets as they are
received, determining the source and destination
device of a packet, and forwarding that packet
appropriately. By delivering messages only to the
connected device that it was intended for, net-
work switches conserve network bandwidth and
offer generally better performance than hubs.
The Switch takes the signal from each computer/
Quantum™ LX and sends it to all of the other
computers/LX panels in your plant or of
fi
ce.
Switches come in several sizes, noted by the
number of ports available -- a four-port Switch
can connect four computers, an eight-port
Switch can connect up to eight computers and
so on. So, if you start with a four-port Switch but
eventually add more panels, you can buy another
Switch and connect it to the one you already
have, increasing the potential number of panels
on your network.
Typical Switch
Note:
If you want to connect one computer to one
Quantum™ LX, you can avoid the switch and use a
crossover Cat 5 cable. With a crossover cable, you di-
rectly connect one Ethernet device to the other with-
out a Switch. To connect more than two you need a
Switch.
Refer to the following pictorial to construct a cross-
over cable:
2
4
6
8
1
3
5
7
Left (Not
Crossed)
1
6
3
4
2 7 8
5
Right (Crossed)
Both Ends of a crossover-cable
CAT-5 Ethernet cable color codes
1 – White w/orange stripe
5 – White w/blue stripe
2 – Orange w/white stripe
6 – Green w/white stripe
3 – White w/green stripe
7 – White w/brown stripe
4 – Blue w/white stripe
8 – Brown w/white stripe
Because of the large number of possible con
fi
gurations in
Summary of Contents for Frick QUANTUM LX
Page 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 12 NOTES ...
Page 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 34 NOTES ...
Page 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 44 NOTES ...
Page 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 60 NOTES ...
Page 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 102 NOTES ...
Page 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 108 NOTES ...
Page 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 116 NOTES ...
Page 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 139 ...