Delay Between Messages
The delay timer on rung 3 must be used when commu-
nicating to the Quantum™ LX with the 100ms preset as
shown. This time delay may be decreased when com-
municating to more than one compressor provided the
messages are alternated between compressors. This time
delay is not required for Quantum™ V. 5.0x or earlier.
Message Read Logic
Use the following logic to read data from the Quantum™
LX panel. To read more data or to read data from several
compressors, copy / paste these rungs as needed then
modify the control block and setup screen parameters
accordingly. The following message read instruction will
be executed whenever counter 5:0 (logic shown above)
is equal to 0.