QUANTUM™ LX COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.020-CS (APRIL 13)
Page 76
Frick®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data
Units
7060
N100:60
47061
R/W
Screen Saver Delay Setpoint
Minutes
7061
N100:61
47062
R/W
Atmospheric Pressure
Pressure (Magnitude)
7100
N101:00
47101
R/W
K Factor
Real
7102
N101:02
47103
R/W
Unload Delay When Stopping
Seconds
7103
N101:03
47104
R/W
Hot Gas On When Below
Percent (%)
7104
N101:04
47105
R/W
False Running Compressor Input Delay
Seconds
7120
N101:20
47121
R/W
Power Assist
Seconds
7121
N101:21
47122
R/W
Power Failure Restart Delay
Minutes
7123
N101:23
47124
R/W
Panel Heater On Value
Temperature
7124
N101:24
47125
R/W
Panel Heater Off Value
7125
N101:25
47126
R/W
Permissive Start Shutdown Delay
Seconds
7126
N101:26
47127
R/W
PLC Interlock Delay
7150
N101:50
47151
R/W
Regulation Mode 1 Setpoint
Pressure
7152
N101:52
47153
R/W
Regulation Mode 1 High Dead Band
Pressure (Magnitude)
7153
N101:53
47154
R/W
Regulation Mode 1 Low Dead Band
7154
N101:54
47155
R/W
Regulation Mode 1 High Proportional Band
7155
N101:55
47156
R/W
Regulation Mode 1 Low Proportional Band
7156
N101:56
47157
R/W
Regulation Mode 1 High Cycle Time
Seconds
7157
N101:57
47158
R/W
Regulation Mode 1 Low Cycle Time
7158
N101:58
47159
R/W
Regulation Mode 1 Auto Cycle Start
Pressure
7159
N101:59
47160
R/W
Regulation Mode 1 Auto Cycle Start Delay
Minutes
7160
N101:60
47161
R/W
Regulation Mode 1 Auto Cycle Stop
Pressure
7161
N101:61
47162
R/W
Regulation Mode 1 Auto Cycle Stop Delay
Minutes
7162
N101:62
47163
R/W
Regulation Mode 1 Load Inhibit
Pressure
7163
N101:63
47164
R/W
Regulation Mode 1 Force Unload
7164
N101:64
47165
R/W
Regulation Mode 1 Shutdown
7165
N101:65
47166
R/W
Regulation Mode 1 Warning
7166
N101:66
47167
R/W
Regulation Mode 1 Shutdown Delay
Seconds
7167
N101:67
47168
R/W
Regulation Mode 1 Warning Delay
7168
N101:68
47169
R/W
Low Suction Pressure Shutdown Mode 1
Pressure
7169
N101:69
47170
R/W
Low Suction Pressure Shutdown Mode 1 Delay
Seconds
7170
N101:70
47171
R/W
Low Suction Pressure Warning Mode 1
Pressure
7171
N101:71
47172
R/W
Low Suction Pressure Warning Mode 1 Delay
Seconds
7172
N101:72
47173
R/W
Low Suction Pressure Mode 1 Load Inhibit
Pressure
7173
N101:73
47174
R/W
Low Suction Pressure Mode 1 Force Unload
7176
N101:76
47177
R/W
Mode 1 Prop Band
Pressure
7177
N101:77
47178
R/W
Mode 1 Integration Time
Seconds
7200
N102:00
47201
R/W
Regulation Mode 2 Setpoint
Temperature
7202
N102:02
47203
R/W
Regulation Mode 2 High Dead Band
Temperature (Magnitude)
7203
N102:03
47204
R/W
Regulation Mode 2 Low Dead Band
SETPOINT VALUES:
Summary of Contents for Frick QUANTUM LX
Page 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 12 NOTES ...
Page 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 34 NOTES ...
Page 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 44 NOTES ...
Page 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 60 NOTES ...
Page 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 102 NOTES ...