QUANTUM™ LX COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.020-CS (APRIL 13)
Page 83
Frick®
Address
AB
Address
Modbus
Address
Read/
Write
Description of Data
Units
7582
N105:82
47583
R/W
Low Separator Temperature Shutdown Delay
Seconds
7583
N105:83
47584
R/W
Low Separator Temperature Warning Delay
7584
N105:84
47585
R/W
Dual Pump Transition Time
7585
N105:85
47586
R/W
Oil Log Shutdown Delay
7586
N105:86
47587
R/W
Dual Pump Transition Time Due To Low Oil Pressure
7587
N105:87
47588
R/W
Separator Velocity Reference
Real
7588
N105:88
47589
R/W
Separator Velocity Ratio
7600
N106:00
47601
R/W
High Filter Shutdown
Pressure (Magnitude)
7601
N106:01
47602
R/W
High Filter Shutdown Delay
Minutes
7602
N106:02
47603
R/W
High Filter Warning
Pressure (Magnitude)
7603
N106:03
47604
R/W
High Filter Warning Delay
Minutes
7604
N106:04
47605
R/W
Condenser High Pressure Override
Pressure
7605
N106:05
47606
R/W
Condenser High Pressure Override Delay
Seconds
7606
N106:06
47607
R/W
Condenser Proportional Band
Pressure (Magnitude)
7607
N106:07
47608
R/W
Condenser Integration Time
Seconds
7608
N106:08
47609
R/W
Condenser High Limit
Percent (%)
7609
N106:09
47610
R/W
Condenser Low Limit
7610
N106:10
47611
R/W
Condenser Control Setpoint
Pressure
7611
N106:11
47612
R/W
Condenser High Dead Band
Pressure (Magnitude)
7612
N106:12
47613
R/W
Condenser Low Dead Band
7613
N106:13
47614
R/W
Condenser High Step Delay
Seconds
7614
N106:14
47615
R/W
Condenser Low Step Delay
7615
N106:15
47616
R/W
Condenser Order Step 1
Integer
7616
N106:16
47617
R/W
Condenser Order Step 2
7617
N106:17
47618
R/W
Condenser Order Step 3
7618
N106:18
47619
R/W
Condenser Order Step 4
7620
N106:20
47621
R/W
Balance Piston On
Percent (%)
7621
N106:21
47622
R/W
Balance Piston Off
7622
N106:22
47623
R/W
Balance Piston Ignore Period
Minutes
7623
N106:23
47624
R/W
Balance Piston Safety Delay
7635
N106:35
47636
R/W
Liquid Slug Warning Setpoint
Temp. (Magnitude)
7636
N106:36
47637
R/W
Liquid Slug Shutdown Setpoint
7640
N106:40
47641
R/W
Liquid Level Setpoint
None
7641
N106:41
47642
R/W
Liquid Level Deadband
7642
N106:42
47643
R/W
Liquid Level Proportional Band
7643
N106:43
47644
R/W
High Liquid Level Delay
Seconds
7650
N106:50
47651
R/W
Liquid Injection On When Above
Temperature
7651
N106:51
47652
R/W
Liquid Injection On Delay
Seconds
7660
N106:60
47661
R/W
Dx Circuit 1 OnWhenAbove
Percent (%)
SETPOINT VALUES (Continued):
Summary of Contents for Frick QUANTUM LX
Page 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 12 NOTES ...
Page 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 34 NOTES ...
Page 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 44 NOTES ...
Page 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 60 NOTES ...
Page 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 102 NOTES ...
Page 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 108 NOTES ...
Page 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 116 NOTES ...
Page 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 139 ...