QUANTUM™ LX COMPRESSOR CONTROL PANEL
COMMUNICATIONS SETUP
090.020-CS (APRIL 13)
Page 21
RETURN FULL LOAD AMPS COMMAND:
#IDA
Command structure:
Command
Description
#
Start command sequence
ID
Compressor
(ID)
code (01, 14, etc.)
A
Return Full Load
(A)
mps command
Returned Answer:
When using the
A
command, the returned Full Load
Amps will be:
XXX = 3 characters followed by a CR, LF.
SLIDE VALVE CONTROL COM-
MANDS:
#IDVLXX
#IDVS
#IDVUXX
Command structure:
Command
Description
#
Start command sequence
ID
Compressor
(ID)
code (01, 14, etc.)
V
Slide
(V)
alve / Slide Stop command
L
(L)
oad Slide Valve command
U
(U)
nload Slide Valve command
XX = 00
Turns selected output off
XX = 01 to
15
Turns selected output on for XX sec-
onds
S
Return
(S)
lide Valve position value
If the command was #01VL00, then the load Slide Valve
output on compressor #1 would be turned off. If the
command was #01VL05, then the load Slide Valve out-
put on compressor #1 would be turned on for 5 seconds,
and would then automatically turn off. NOTE: the Slide
Valve must be in the remote mode for this command
to be executed. Time is not accrued, each command
restarts timer.
Returned Answer (for L or U commands):
Character
Position
Description of returned data
1
(A)
cknowledge
2, 3
(ID)
code veri
fi
ed
(Carriage return, line feed.)
Returned Answer (for S command):
Character
Position
Description of returned data
1, 2, 3
Slide Valve position.
CR, LF (Carriage return, line feed)
RETURN SLIDE STOP POSITION COMMAND:
#IDVP
Command structure:
Command
Description
#
Start command sequence
ID
Compressor
(ID)
code (01, 14, etc.)
V
Slide
(V)
alve / Slide Stop command
P
Return Slide Stop (P)osition value
Returned Answer:
Character
Position
Description of returned data
1, 2
Slide Stop position, i.e. 25 = 2.5
CR, LF (Carriage return, line feed)
CHANGE COMPRESSOR MODE
COMMAND:
#IDMCmID
Command structure:
Command
Description
#
Start command sequence
ID
Compressor
(ID)
code (01, 14, etc.)
MC
Change
(M)
ode of
(C)
ompressor
m
=
O (O)
ff
=
A (A)
uto
=
R (R)
emote
ID
(ID)
code repeated for veri
fi
cation
Returned Answer:
Character
Position
Description
1
(A)
cknowledge
2, 3
(ID)
code veri
fi
ed
(Carriage return, line feed)
Summary of Contents for Frick QUANTUM LX
Page 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 12 NOTES ...
Page 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 34 NOTES ...
Page 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 44 NOTES ...
Page 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 60 NOTES ...
Page 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 102 NOTES ...
Page 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 108 NOTES ...
Page 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 116 NOTES ...
Page 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 139 ...