Address
AB
Address
Modbus
Address Read/Write
Description of Data
Analog
Board #
Channel
#
Module
Type
3000
N30:0
43001
R
Calculated Capacity
Percent (%)
3006
N30:6
43007
R
Filter Differential Pressure
Pressure (Magnitude)
3008
N30:8
43009
R
System Compression Ratio
Percent (%)
3018
N30:18
43019
R
Current Runtime
Hours
3019
N30:19
43020
R
Suction Superheat
Temperature (Magnitude)
3020
N30:20
43021
R
Discharge Superheat
3021
N30:21
43022
R
Percent of Full Load Amps
Percent (%)
3033
N30:33
43034
R
Volume High End
Volts
3034
N30:34
43035
R
Volume Current Value
3035
N30:35
43036
R
Volume Low End
3036
N30:36
43037
R
Capacity High End
3037
N30:37
43038
R
Capacity Current Value
3038
N30:38
43039
R
Capacity Low End
3039
N30:39
43040
R
Calculated Volume Ratio
Real
3058
N30:58
43059
R
Calculated Volume Ratio (Suction)
Real
3059
N30:59
43060
R
Calculated Volume Ration (Economizer)
3060
N30:60
43061
R
Current Regulation Value
Pressure
3061
N30:61
43062
R
Current Regulation Setpoint
3062
N30:62
43063
R
Estimated Kilowatts
kW
3063
N30:63
43064
R
Panel Temperature
Temperature
3070
N30:70
43071
R
Safety #1 Message (Most Recent)
Note
1
Integer
3071
N30:71
43072
R
Safety #2 Message
3072
N30:72
43073
R
Safety #3 Message
3073
N30:73
43074
R
Safety #4 Message
3074
N30:74
43075
R
Safety #5 Message
3075
N30:75
43076
R
Safety #6 Message
3076
N30:76
43077
R
Safety #7 Message
3077
N30:77
43078
R
Safety #8 Message
3078
N30:78
43079
R
Safety #9 Message
3079
N30:79
43080
R
Safety #10 Message
3080
N30:80
43081
R
Total Run Time (Thousands)
Note
2
Real
3081
N30:81
43082
R
Total Run Time (Units)
3102
N31:02
43103
R
Coalescer Filter Differential
Pressure (Magnitude)
Note 1:
Refer to the chart of
WARNING/SHUTDOWN MESSAGE CODES
on pages 103-107 to determine which message is being
displayed.
Note 2:
To calculate the Total Run Time, use the following equation:
Total Run Time (Thousands) x 1000 + Total Run Time (Units) = Total Run Time
CALCULATED VALUES:
Summary of Contents for Frick QUANTUM LX
Page 12: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 12 NOTES ...
Page 34: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 34 NOTES ...
Page 44: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 44 NOTES ...
Page 60: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 60 NOTES ...
Page 102: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 102 NOTES ...
Page 108: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 108 NOTES ...
Page 116: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 116 NOTES ...
Page 139: ...QUANTUM LX COMPRESSOR CONTROL PANEL COMMUNICATIONS SETUP 090 020 CS APRIL 13 Page 139 ...