34 | BA-40100-02-V17
TOPAX
®
DX
Multichannel controller
19.1.8 Adjustment of shock chlorination
For shock chlorination, the "Disinfection" controller is switched to manu-
al operation for an adjustable time and an adjustable dosing rate. When
the time has elapsed, the controller automatically switches to automatic
operation.
NOTE
The user must empirically define the time and the
dosing rate for shock chlorination before this func-
tion is performed.
The "shock chlorination" key is used at the same time for configuring
and starting shock chlorination. Set the time with the "Time" key. Set the
maximum output capacity with the "%" key.
Press the "OK" key to save the settings. The shock chlorination is indi-
cated on the status display. The timer counts down and indicates the
remaining time in minutes. When the time has elapsed, the system
switches to automatic operation.
19.1.9 Menu 2.2: Alarms
mg/l
mV
pH
039 702 719 09
0
ESC
disinfection
pH value
REDOX
temperature
next
setup
mg/l
alarms
2.2
Fig. 35: Main menu >> Menu 2 >> alarms
mg/l
mV
pH
039 702 719 09
0
ESC
comb. cl.
% salt
alarms
setup
2.2
Fig. 36: Main menu >> Menu 2 >> alarms >> next >> page 2 of alarms(with
more than five inputs)
The TOPAX DX monitors its inputs (see chapter “9 Alarms” on
page 26). If an unwanted alteration appears on an input value, the
alarm is set off. The alarm-setting is configured in this menu:
Menu
Function
Required specifications
2.2.1
Disinfection
2.2.1.1
Maximum alarm
ON or OFF + limit value
2.2.1.2
Minimum Alarm
ON or OFF + limit value
2.2.1.3
Y alarm
ON or OFF + time
2.2.1.4
Alarm delay
ON or OFF + time
2.2.2
pH value
2.2.2.1
Maximum alarm
ON or OFF + limit value
2.2.2.2
Minimum Alarm
ON or OFF + limit value
2.2.2.3
Y alarm
ON or OFF + time
2.2.2.4
Alarm delay
ON or OFF + time
2.2.3
Redox potential
2.2.3.1
Maximum alarm
ON or OFF + limit value
2.2.3.2
Minimum Alarm
ON or OFF + limit value
2.2.3.4
Alarm delay
ON or OFF + time
2.2.4
Temperature
2.2.4.1
Maximum alarm
ON or OFF + limit value
2.2.4.2
Minimum Alarm
ON or OFF + limit value
2.2.4.4
Alarm delay
ON or OFF + time
2.2.5
combinded chlorine
2.2.5.1
Maximum alarm
ON or OFF + limit value
2.2.5.2
Minimum Alarm
ON or OFF + limit value
2.2.5.3
Y alarm
ON or OFF + time
2.2.5.4
Alarm delay
ON or OFF + time
2.2.6
Salt content
2.2.6.1
Maximum alarm
ON or OFF + limit value
2.2.6.2
Minimum Alarm
ON or OFF + limit value
2.2.6.3
Y alarm
ON or OFF + time
2.2.6.4
Alarm delay
ON or OFF + time
Select one of the six inputs. The device goes to the relevant Menu 2.2.2-
2.2.5 and shows the actual configuration of the input alarm.
Select one of the (up to) four available alarm functions of the input for
configuration.
Alarm
Alarm is set off, if &
Key
Maximum measuring
value
Input value > max. value
max alarm
Minimum measuring
value
Input value < min. value
min alarm
Y alarm
after a given time for the input of the
relevant control unit in the computer
s output service is > 95%.
Y alarm
Alarm delay time
the alarm s delay time has run out
Delay
Fig. 37: Possible alarm functions of the six inputs.
Press on "OFF" to turn off the chosen alarm function. Confirm twice with
the “OK” key.
Press on "ON" to turn the chosen alarm function on.
Enter the requested limit value.