46 | BA-40100-02-V17
TOPAX
®
DX
Multichannel controller
20.1.8 Example 7:
PC - connection to computer network
ATTENTION!
The data line must be locked at both sides with a
120 Ohm line resistance and must be supplied a
firm potential using the two link plugs on the two
jumpers on the circuit board of the display of all la-
test TOPAX versions.
For this reason, two link plugs have to be installed on
the display circuit board of the last TOPAX DX (see
chapter “4.9 First set-up and programming guide-
lines” on page 14).
On the sides of the PC; the load resistor has to be
plugged at the connector converter.
DO4 DO3 DO2 DO1
78404
78403
78402
DO7
DO6
DO5
DO0
78399
B
A
78406
Rechnerschnittstelle
+
-
+
-
+
-
+
-
+
-
+
-
+
-
+
-
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
20 mA
Stromausgänge
digitale Eingänge
36
37
38
PE
N
L
Netzteil
33
34
92
93
94
87
88
89
90
91
86
-
+
81
82
83
84
85
-
-
+
+
Alarmrelais
39
40
41
43
44
45
46
42
35
95
96
B
A
Maximale Länge des Netzwerks: 1000m
Hilfsspannung 5 VDC
(USB Steckverbinder)
120 Ohm
Abschlusswiderstand
Converter
RS232 <=> RS485
Bestell-Nr
. 44300101
RS 232 (9polig)
Computer
(T
opV
iew Software)
Displayplatine
120
Ohm Abschlusswiderstand
auf AN
Pull-Up / Pull-Down Widerstände auf
AN
-> Beide Jumper auf ON
(siehe Kapitel 4.4)
Letzter
T
OP
AX DX im Netzwerk
(maximal 14 Geräte)
T
OP
AX
(DX, DE, L, LF
, N, NT)
B
A
T
OP
AX
(DX, DE, L, LF
, N, NT)