UMG 605-PRO
www.janitza.de
73
Address
Designation
Setting range
Unit
Default
200
Device address, Modbus/Profibus
1 to 255
-
1
201
Baud rate, RS232
0 = 9600Bit/s
1 = 19200Bit/s
2 = 38400Bit/s
3 = 57600Bit/s
4 =115200Bit/s
0 to 4
-
4
202
Baud rate, RS485
0 = 9600Bit/s
1 = 19200Bit/s
2 = 38400Bit/s
3 = 57600Bit/s
4 =115200Bit/s
5 = 921600Bit/s
0 to 5
-
4
203
RS485, mode
0 = Modbus RTU/slave
1 = Modbus RTU/master
2 = Gateway transparent
3,4 = internal use
0 to 6
-
0
204
RS232, mode 0 to 6 0
0 = Modbus RTU/slave
3 = Debug
6 = SLIP
(for internal use only)
0 to 6
-
0
Address
Designation
Setting range
Unit
Default
205
DHCP mode
0 = static IP
1 = BootP
2 = DHCP client
3 = Zeroconf
0 to 3
-
2
300
IP address, xxx --- --- ---
0 to 255
-
000
301
IP address, --- xxx --- ---
0 to 255
-
000
302
IP address, --- --- xxx ---
0 to 255
-
000
303
IP address, --- --- --- xxx
0 to 255
-
000
304
IP mask, xxx --- --- ---
0 to 255
-
000
305
IP mask, --- xxx --- ---
0 to 255
-
000
306
IP mask, --- --- xxx ---
0 to 255
-
000
307
IP mask, --- --- --- xxx
0 to 255
-
000
310
IP gateway, xxx --- --- ---
0 to 255
-
000
311
IP gateway, --- xxx --- ---
0 to 255
-
000
312
IP gateway, --- --- xxx ---
0 to 255
-
000
313
IP gateway, --- --- --- xxx
0 to 255
-
000
Table Parameter list for bus settings
Table Parameter list for Ethernet settings
Summary of Contents for UMG 605 PRO
Page 7: ...www janitza de UMG 605 PRO 2...
Page 19: ...www janitza de UMG 605 PRO 14...
Page 33: ...www janitza de UMG 605 PRO 28...
Page 37: ...www janitza de UMG 605 PRO 32...
Page 51: ...www janitza de UMG 605 PRO 46...
Page 53: ...www janitza de UMG 605 PRO 48...
Page 63: ...www janitza de UMG 605 PRO 58...
Page 75: ...www janitza de UMG 605 PRO 70...
Page 81: ...www janitza de UMG 605 PRO 76...
Page 85: ...www janitza de UMG 605 PRO 80...
Page 87: ...www janitza de UMG 605 PRO 82...