UMG 605-PRO
22
KTY83
6. 7
Temperature measurement
The device has a temperature measurement
input that is designed for a maximum total
burden of 4 kOhm.
Fig.42.1 Example, temperature measurement with
a KTY83.
UMG 605-PRO
Analog Input
m
CAUTION!
Transmission errors and
damage to property due
to electrical faults
If the line is longer than 30 m, there
is an increased probability of transmission
errors and damage to the device due
to atmospheric discharge.
Use a shielded cable to connect
to the temperature sensor.
m
CAUTION!
Risk of injury due
to electric voltage!
Insuffi cient insulation of the operating
equipment at the temperature measurement
input to the mains supply circuits can cause
the temperature measurement input
and interfaces RS232 and RS485 to
be hazardous to touch.
Ensure that there is reinforced or double
insulation to the mains supply circuits!
Fig. Connecting temperature sensor to the measurement
input
c
WARNING!
Risk of injury due
to electric voltage!
RS232, RS485 and the temperature
measurement input are not galvanically
separated from each other.
Therefore, be aware that hazardous
voltages on the inputs that are not
galvanically separated may have effects
on the other connections.
Summary of Contents for UMG 605 PRO
Page 7: ...www janitza de UMG 605 PRO 2...
Page 19: ...www janitza de UMG 605 PRO 14...
Page 33: ...www janitza de UMG 605 PRO 28...
Page 37: ...www janitza de UMG 605 PRO 32...
Page 51: ...www janitza de UMG 605 PRO 46...
Page 53: ...www janitza de UMG 605 PRO 48...
Page 63: ...www janitza de UMG 605 PRO 58...
Page 75: ...www janitza de UMG 605 PRO 70...
Page 81: ...www janitza de UMG 605 PRO 76...
Page 85: ...www janitza de UMG 605 PRO 80...
Page 87: ...www janitza de UMG 605 PRO 82...