7.
Interfaces
The device has the following interfaces:
• RS232
• RS485
• Ethernet
• Profibus
All interfaces can be used simultaneously.
7. 1
Shielding
A twisted, shielded cable should be used
for connections via the RS232 and RS485
interfaces.
Earth the shields of all cables that lead
to the cabinet and at the cabinet entry.
Connect the screens over a generous area
and in a manner that will conduct well,
to a low-noise earth.
Gather the cables mechanically above
the earthing clamp in order to avoid damage
due to cable movements.
Use suitable cable glands to feed the cables
into the cabinet, for example, armoured
conduit couplings.
Fig. Shielding procedure at cabinet entry.
Cable
Strain relief
Screen braid of the cable
Earthing clamp
Noiseless ground
c
WARNING!
Risk of injury due
to electric voltage!
RS232, RS485 and the temperature
measurement input are not galvanically
separated from each other. The Profibus
and Ethernet are functionally insulated from
each other and the remaining interfaces.
Therefore, be aware that hazardous
voltages on the inputs that are not
galvanically separated may have effects
on the other connections.
Summary of Contents for UMG 605 PRO
Page 7: ...www janitza de UMG 605 PRO 2...
Page 19: ...www janitza de UMG 605 PRO 14...
Page 33: ...www janitza de UMG 605 PRO 28...
Page 37: ...www janitza de UMG 605 PRO 32...
Page 51: ...www janitza de UMG 605 PRO 46...
Page 53: ...www janitza de UMG 605 PRO 48...
Page 63: ...www janitza de UMG 605 PRO 58...
Page 75: ...www janitza de UMG 605 PRO 70...
Page 81: ...www janitza de UMG 605 PRO 76...
Page 85: ...www janitza de UMG 605 PRO 80...
Page 87: ...www janitza de UMG 605 PRO 82...