UMG 605-PRO
www.janitza.de
39
11. 4
RS232 configuration
The following data must be programmed
to operate the RS232 interface:
• baud rate,
• operating mode.
For information on the factory default setting
and the setting ranges, see the parameter list
in the appendix.
Address
Settings
201
Baud rate, RS232
0 = 9600Bit/s
1 = 19200Bit/s
2 = 38400Bit/s
3 = 57600Bit/s
4 =115200Bit/s
204
RS232. mode
0 = Modbus RTU/slave
3 = Debug
6 = SLIP
(for internal use only)
Address
Settings
200
Device address (1 to 255)
applies to Modbus and Profibus
1 = factory default setting
202
Baud rate, RS485
0 = 9600Bit/s
1 = 19200Bit/s
2 = 38400Bit/s
3 = 57600Bit/s
4 =115200Bit/s
5 = 921600Bit/s
203
RS485, mode
0 = Modbus RTU/slave
1 = Modbus RTU/master
2 = Gateway transparent
11. 5
RS485 configuration
The following data must be programmed
to operate the RS485 interface:
• device address,
• baud rate,
• operating mode.
For information on the factory default setting
and the setting ranges, see the parameter list
in the appendix.
Summary of Contents for UMG 605 PRO
Page 7: ...www janitza de UMG 605 PRO 2...
Page 19: ...www janitza de UMG 605 PRO 14...
Page 33: ...www janitza de UMG 605 PRO 28...
Page 37: ...www janitza de UMG 605 PRO 32...
Page 51: ...www janitza de UMG 605 PRO 46...
Page 53: ...www janitza de UMG 605 PRO 48...
Page 63: ...www janitza de UMG 605 PRO 58...
Page 75: ...www janitza de UMG 605 PRO 70...
Page 81: ...www janitza de UMG 605 PRO 76...
Page 85: ...www janitza de UMG 605 PRO 80...
Page 87: ...www janitza de UMG 605 PRO 82...