www.janitza.de
UMG 605-PRO
38
11. 2
Current transformer ratio
You can set the current transformer ratio
for the baseline measurement using
addresses 000 and 001.
You can use addresses 010 and 011
to set the current transformer ratio for
the supporting measurement.
A current transformer ratio of 5 A / 5 A is
factory-set for all 4 current transformer inputs
in the factory.
Address
Current transformer
values
Baseline measurement
000
L1 L2 L3 (primary)
001
L1 L2 L3 (secondary)
Supporting measurement
010
L4 (primary)
011
L4 (secondary)
Address
Content
PRG
Fig. Example; Current transformer (primary) for the baseline
measurement, address 000 with a content of “5“.
11. 3
Voltage transformer ratio
You can use addresses 002 and 003 to set
the voltage transformer ratio for the baseline
measurement.
You can use addresses 012 and 013
to set the voltage transformer ratio for
the supporting measurement.
A voltage transformer ratio of 400 V / 400 V is
factory-set for all 4 voltage transformer inputs
in the factory.
Address
Current transformer
values
Baseline measurement
002
L1 L2 L3 (primary)
003
L1 L2 L3 (secondary)
Supporting measurement
012
L4 (primary)
013
L4 (secondary)
Fig. Example; voltage transformer (primary) for the baseline
measurement, address 002 with a content of “400“.
Address
Content
PRG
Summary of Contents for UMG 605 PRO
Page 7: ...www janitza de UMG 605 PRO 2...
Page 19: ...www janitza de UMG 605 PRO 14...
Page 33: ...www janitza de UMG 605 PRO 28...
Page 37: ...www janitza de UMG 605 PRO 32...
Page 51: ...www janitza de UMG 605 PRO 46...
Page 53: ...www janitza de UMG 605 PRO 48...
Page 63: ...www janitza de UMG 605 PRO 58...
Page 75: ...www janitza de UMG 605 PRO 70...
Page 81: ...www janitza de UMG 605 PRO 76...
Page 85: ...www janitza de UMG 605 PRO 80...
Page 87: ...www janitza de UMG 605 PRO 82...