Setting the module’s addresses (Pro I modules, too)
ADwin
12
ADwin-Pro II
Hardware, manual Dec. 2018
Setting the module’s adress: Pro I modules
With Pro I modules, you set the module address manually via DIP-switches.
The on-board block of DIP-switches is located right to the bottom.
Wit 8 DIP switches the address is selectable between 1 and 255 (see fig. 12).
Each module of the same group needs to have a different address.
Please note:
– A RSxxx module with 4 serial interfaces uses 2 addresses (group EXT):
the set address and the following address.
– A fieldbus module uses 32 addresses (group EXT); the address alloca-
tion is shown in fig. 13.
Module no.
Settings of DIP switches
1
2
3
4
5
6
7
8
1
1
0
0
0
0
0
0
0
2
0
1
0
0
0
0
0
0
3
1
1
0
0
0
0
0
0
4
0
0
1
0
0
0
0
0
5
1
0
1
0
0
0
0
0
6
0
1
1
0
0
0
0
0
7
1
1
1
0
0
0
0
0
8
0
0
0
1
0
0
0
0
…
…
254
0
1
1
1
1
1
1
1
255
1
1
1
1
1
1
1
1
Fig. 12 – Address settings of the
ADwin-Pro
modules with DIP switches
ON
1 2 3 4 5 6 7 8
A0 A1 A2 A3 A4 A5 A6 A7
ON
1 2 3 4 5 6 7 8
DIP-switch block
Set module
address
Addit. allocated
addresses
Settings of DIP switches
1
2
3
4
5
6
7
8
1
160…191
1
0
0
0
0
0
0
0
2
192…223
0
1
0
0
0
0
0
0
3
224…255
1
1
0
0
0
0
0
0
4
128…159
0
0
1
0
0
0
0
0
Fig. 13 – Address settings of fieldbus modules with DIP switches