27
Types of identificators
Press
[2] [0] [#]
in programming mode. Green LEDs 2 and 3 reflect current
settings, LED 2 corresponds to ASK modulation identificators compatibility, and LED
3 corresponds to FSK modulation identificators compatibility. Then enter identificator
type +
[#]
.
Identificators' types
[1]
- ASK identificators,
[2]
- FSK identificators,
[3]
- FSK and ASK identificators simultaneously.
For example: It is necessary to program the panel for simultaneous utilization of
ASK and FSK identificators.
When been in engineer code programing mode press
[2]
[0] [#]
(green LEDs 2 and
3 reflect current settings). Press
[3] [#],
new value is accepted, the panel turns to
upper menu level (red LEDs 1 and 2 blink alternately, LED3 is off).
Press
[#]
button to exit the programming mode and turn to the main one (LED2 blinks
red).
Readers operation
Press
[2] [1] [#]
in programming mode. Green LEDs 2 and 3 reflect current settings,
LED 2 corresponds to external reader operation, and LED 3 corresponds to internal
reader operation. Then enter [readers' operation mode] +
[#]
.
Readers' operation modes:
[1]
- external reader operation solely (LED 2)
[2]
- internal reader operation solely (LED 3)
[3]
- both readers simultaneous operation
For example: It is necessary to program the panel for external reader use.
When been in engineer code programming mode press
[2]
[1] [#]
(green LEDs 2
and 3 reflect current setting). Press
[1] [#]
, new value is accepted, the panel
switches to upper menu level (red LEDs 1 and 2 blink alternately, LED 3 is off).
At next
[#]
button pressing the panel exits programming mode and switches to
the main one (LED2 blinks red).
40 seconds pause between digits entry causes panel switching to main mode.
Setting control panel address
Press
[2] [2] [#]
in programming mode, buzzer and green LED 3 indicate current
panel address settings. The panel turns to upper menu level after
[#]
button
pressing. To introduce new settings press
[*]
, enter [address] (from 0 to 31) and
[#]
.
For example: It is necessary to set panel address for 8.
In engineer code programming mode press
[2]
[2] [#]
, buzzer and green LED3
reflect current address setting. Press
[8] [#]
, new value is accepted, the panel
turns to upper menu level (red LEDs 1 and 2 blink alternately, LED3 is off.
Press
[#]
to exit programming mode and move to the main mode.
40 seconds pause between digits entry causes panel switching to main mode.
Programming the panel in stand-alone use