2.
Apply some antioxidant onto the metal surface.
3.
Mount the lug on the grounding posts, replace the spring-washers and fasten the bolts.
Avoid using excessive torque.
CAUTION
Do not remove the earth connection unless all power supply connections are disconnected.
DANGER
Before connecting power to the platform, make sure that the grounding posts are firmly
connected to a reliable ground, as described below.
3.3 Connecting to a Power Source
CAUTION
Please refer to the iSG18GFP installation guide for complete installation instructions.
3.3.1 Wiring DC Input Voltage Feed
Input voltage can be either AC or DC depending on the specific module you purchased. Carefully review the label on
the back of the module.
For the DC version, there are 2 connection inputs. They are marked as "PWR A" and "PWR B". For proper operation,
it is only necessary to connect one power source, either to "PWR A" or to "PWR B". However, for redundancy
purposes you may connect 2 different power sources—one at "PWR A" and the second to "PWR B".
For wiring the voltage, an opposite plug connector (2 pcs) is supplied.