The base plate of the Indoor humidity/temperature sensor is mounted directly on the wall.
The batteries are then inserted into the housing and the housing is hooked into the installed base
plate by means of a snap-in connection.
44
inVENTer Connect controller platform | Installation instructions
INSTALLING THE DEVICES
Installing the FTS19-Connect Indoor Humidity/Temperature Sensor
Select the installation location of the Indoor humidity/temperature sensor at medium room height.
The measured values at the installation site must correspond to those of the room in order to
obtain accurate measurement results. The sensor must not be exposed to direct sunlight.
Ensure that the installation location of the Indoor humidity/temperature sensor is no more than 20
m from the controller.
Spirit level, pencil, drill with 6 mm drill bit, dowels (2x)
Requirements:
• The masonry must be dry and in a load-bearing
condition.
• Plasterboard wall is completed.
• No lintels in the location of the planned drill holes.
►
Hold the base plate at the installation location and
level it with a spirit level.
►
Mark the drill holes.
The drilling template is prepared.
►
Drill the dowel holes at the markings.
►
Insert the dowels.
The wall is prepared for screwing on the base plate.