inVENTer Connect controller platform | Installation instructions
INSTALLING THE DEVICES
Connecting the data cable (only for communication between system devices by
cable)
Stripping tool, small slotted screwdriver
Requirements:
• An RS485 data cable has been laid.
• The holding plate is mounted in the housing.
• The mains cable and fan cable are connected.
►
Shorten the RS485 data cable to the required
length and strip approx. 7 mm of insulation with the
stripping tool.
►
Connect this cable (red/yellow) to the holding plate:
• Signal cable A (red) to "A".
• Signal cable B (yellow) to "B"
The RS485 data cable is installed.
If an RS485 data cable is used for communication between the controller and the ventilation
devices and/or CO
2
sensor, the jumpers for the
first
(Easy Connect e16)
and last devices in the
line
must be set as shown below.
Position of jumper on the Connect inner cover
RS485
Signalleitung A
Signalleitung B
A B
1 Slot for the jumper
2 Jumper connected
The 2-pin connector for the jumper is located
on the holding plate of the inner cover.
On delivery, the jumper is only plugged into
one pin (deactivated) or is included as an
accessory.
Use the two pins to activate the connection
with the RS485 data cable.
A
B
Red
Yellow
2
1