inVENTer Connect controller platform | Installation instructions
INSTALLING THE DEVICES
Only when using an RS485 data cable
Position of the pin connectors for the jumper
Easy Connect e16 controller and CS2-Connect CO
2
sensor jumpers
If an RS485 data cable is used for communication between the controller and the ventilation
devices and/or CO
2
sensor, the jumpers must be set
for the first and last devices in the line
as
shown below.
1 Slot for the jumper
2 Jumper connected
The 3-pin connector for the jumper is located
on the rear of the programming unit.
On delivery, the jumper is plugged into the first
two pins from the left (RS485 deactivated).
Use the first two pins from the right to activate
the RS485 data cable connection.
The marking on the housing also serves as a
guide:
I = RS485 activated
O = RS485 deactivated
2
1