Member objects
5.2.1 Type: Gateway
Object-name
Description
Object-type
Object-instance
MH-RC-BAC-1
Mitsubishi Heavy Industries RC Interface
Device
246000*
5.2.2 Type: Indoor Unit
Object-name
Description
Object-type
Object-instance
OnOff_status
BI
0
OnOff_command
BO
0
Mode_status
MI
0
Mode_command
MO
0
SetPoint_status
AI
0
SetPoint_command
AO
0
FanSpeed_status
MI
1
FanSpeed_command
MO
1
AirDirectionUD_status
MI
2
AirDirectionUD_command
MO
2
RoomTemperature_status
AI
1
RoomTemperature_command
AO
1
ErrorCode
AI
2
ErrorCodeM
MI
4
ErrorActive
BI
1
ErrorAddress
AI
4
ErrorReset
BO
5
OnTimeCounter
AV
0
FilterSign
BI
6
FilterReset
BO
4
Occupancy
MV
0
OccupiedCoolSetPoint
AV
1
OccupiedHeatSetPoint
AV
2
UnoccupiedCoolSetPoint
AV
3
UnoccupiedHeatSetPoint
AV
4
OccupancyContinuousCheck
BV
0
UnoccupiedDeadbandAction
BV
1
LockRemoteControl
BV
2
OutdoorTemp_status
AI
8
CenterRemote
MI
9
* This is the default value. Check section 5.3 (below) for more information.