5.3.7 Setpoint_command (Analog Output Object Type)
It sets the desired temperature in the indoor unit.
Property Identifier
Property Datatype
Value
ASHRAE IBOX
Object_Identifier
BACnetObjectIdentifier
(Analog Output, 0)
R
R
Object_Name
CharacterString
“SetPoint_command”
R
R
Object_Type
BACnetObjectType
ANALOG_OUTPUT (1)
R
R
Present_Value
REAL
16…32 ºC
60…90 ºF
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Update_Interval
Unsigned
-
O
-
Units **
BACnetEngineeringUnits
Degrees Celsius (62),
Degrees Fahrenheit (64)
R
R
Min_Pres_Value
REAL
16 ºC // 60 ºF
O
R
Max_Pres_Value
REAL
32 ºC // 90 ºF
O
R
Resolution
REAL
-
O
-
COV_Increment
REAL
0
O
W
Priority_Array
BACnetPriorityArray
BACnetPriorityArray
R
R
Relinquish_Default
Unsigned
22
R
R
Time_Delay
Unsigned
-
O
-
Notification_Class
Unsigned
-
O
-
High_Limit
REAL
-
O
-
Low_Limit
REAL
-
O
-
Deadband
REAL
-
O
-
Limit_Enable
BACnetLimitEnable
-
O
-
Event_Enable
BACnetEventTransitionBits
-
O
-
Acked_Transitions
BACnetEventTransitionBits
-
O
-
Notify_Type
BACnetNotifyType
-
O
-
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
-
Profile_Name
CharacterString
-
O
-
** Use of Celsius or Fahrenheits units can be selected throught the switch configuration. Check section 6.1 for more information.