IntesisBox
®
BACnet
– RAC, FD, KX6 and KXR6 (VRF) series
User Manual r1.0 eng
URL
tel
http://www.intesisbox.com
[email protected]
+34 938047134
40/60
© Intesis Software S.L.U. - All rights reserved
IntesisBox
is a registered trademark of Intesis Software SLU
5.3.23 OccupiedCoolSetPoint (Analog Value Object Type)
It indicates the current Setpoint when Cool mode is selected and Occupancy is enabled and the room is occupied.
Check section 7.4 for more information.
Property Identifier
Property Datatype
Value
ASHRAE
IBOX
Object_Identifier
BACnetObjectIdentifier
(Analog Value, 1)
R
R
Object_Name
CharacterString
“OccupiedCoolSetPoint”
R
R
Object_Type
BACnetObjectType
ANALOG_VALUE (2)
R
R
Present_Value
REAL
16…32 ºC
60…90 ºF
R
R
Description
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Update_Interval
Unsigned
-
O
-
Units **
BACnetEngineeringUnits
Degrees Celsius (62)
Degrees Fahrenheit (64)
R
R
Min_Pres_Value
REAL
-
O
-
Max_Pres_Value
REAL
-
O
-
Resolution
REAL
-
O
-
COV_Increment
REAL
0
O
W
Time_Delay
Unsigned
-
O
-
Notification_Class
Unsigned
-
O
-
High_Limit
REAL
-
O
-
Low_Limit
REAL
-
O
-
Deadband
REAL
-
O
-
Limit_Enable
BACnetLimitEnable
-
O
-
Event_Enable
BACnetEventTransitionBits
-
O
-
Acked_Transitions
BACnetEventTransitionBits
-
O
-
Notify_Type
BACnetNotifyType
-
O
-
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
-
Profile_Name
CharacterString
-
O
-
** Use of Celsius or Fahrenheits units can be selected throught the switch configuration. Check section 6.1 for more information.