IntesisBox
®
BACnet
– RAC, FD, KX6 and KXR6 (VRF) series
User Manual r1.0 eng
URL
tel
http://www.intesisbox.com
[email protected]
+34 938047134
19/60
© Intesis Software S.L.U. - All rights reserved
IntesisBox
is a registered trademark of Intesis Software SLU
5.3.3 OnOff_command (Binary Output Object Type)
It sets the indoor unit to On or Off.
Property Identifier
Property Datatype
Value
ASHRAE IBOX
Object_Identifier
BACnetObjectIdentifier
(Binary Output, 0)
R
R
Object_Name
CharacterString
“
OnOff_command
”
R
R
Object_Type
BACnetObjectType
BINARY_OUTPUT (4)
R
R
Present_Value
BACnetBinaryPV
INACTIVE (0) / ACTIVE (1)
W
W
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Polarity
BACnetPolarity
NORMAL (0)
R
R
Inactive_Text
CharacterString
"Off"
O
R
Active_Text
CharacterString
“On"
O
R
Change_Of_State_Time
BACnetDatetime
-
O
-
Change_Of_State_Count
Unsigned
-
O
-
Time_Of_State_Count_Reset
BACnetDatetime
-
O
-
Elapsed_Active_Time
Unsigned
-
O
-
Time_Of_Active_Time_Reset
BACnetDatetime
-
O
-
Minimum_Off_Time
Unsigned32
-
O
-
Minimum_On_Time
Unsigned32
-
O
-
Priority_Array
BACnetPriorityArray
BACnetPriorityArray
R
R
Relinquish_Default
BACnetBinaryPV
INACTIVE (0)
R
R
Time_Delay
Unsigned
-
O
-
Notification_Class
Unsigned
-
O
-
Feedback_Value
BACnetBinaryPV
-
O
-
Event_Enable
BACnetEventTransitionBits
-
O
-
Acked_Transitions
BACnetEventTransitionBits
-
O
-
Notify_Type
BACnetNotifyType
-
O
-
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
-
Profile_Name
CharacterString
-
O
-