Connect to BACnet IP
Connect the RJ45 connector to the Ethernet connection (ETH) of MH-RC-BAC-1.
Respect same recommendations as per any other Ethernet communication network.
Remember to activate the IP interface through the
SW3
switch.
By default, the MH-RC-BAC-1 comes with a static IP address:
192.168.100.246
.
In order to change it, please use the configuration tool and select either DHCP or another static IP (recommended)
that suits your integration project requirements. Check section 7.5 for more information.
6.3.1 BACnet Device Instance
If the “Auto Device Instance” is used, keep in mind that the Device Instance will be build using the “Device Instance
Base” + the address selected in SWP2 P1-P7.
Binary value
b
7
…b
0
Decimal value
Switches
1 2 3 4 5 6 7 8
MAC address
0000000x
0
x
0
1000000x
1
x
1
0100000x
2
x
2
1100000x
3
x
3
….
….
….
…
1011111x
125
x
125
0111111x
126
x
126
1111111x
127
x
127
Binary value
b
7
…b
0
Decimal value
Switches
1 2 3 4 5 6 7 8
Description
0xxxxxxx
0
x x x x x x x
BACnet MS/TP active (default value)
1xxxxxxx
1
x x x x x x x
BACnet IP active
Important
: Remember that switch changes only apply after an IntesisBox power cycle