5.3.14 ErrorCode (Analog Input Object Type)
It indicates the current error present in the AC system.
Property Identifier
Property Datatype
Value
ASHRAE IBOX
Object_Identifier
BACnetObjectIdentifier
(Analog Input, 2)
R
R
Object_Name
CharacterString
“
ErrorCode
”
R
R
Object_Type
BACnetObjectType
ANALOG_INPUT (0)
R
R
Present_Value
REAL
-1
…
92*
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Update_Interval
Unsigned
300
O
-
Units
BACnetEngineeringUnits
NO_UNITS (95)
R
R
Min_Pres_Value
REAL
-
O
-
Max_Pres_Value
REAL
-
O
-
Resolution
REAL
-
O
-
COV_Increment
REAL
0
O
W
Time_Delay
Unsigned
-
O
-
Notification_Class
Unsigned
-
O
-
High_Limit
REAL
-
O
-
Low_Limit
REAL
-
O
-
Deadband
REAL
-
O
-
Limit_Enable
BACnetLimitEnable
-
O
-
Event_Enable
BACnetEventTransitionBits
-
O
-
Acked_Transitions
BACnetEventTransitionBits
-
O
-
Notify_Type
BACnetNotifyType
-
O
-
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
-
Profile_Name
CharacterString
-
O
-
* Check section 0 for more information about each error code.