5.3.13 RoomTemperature_command (Analog Output Object Type)
It sets the room temperature to be used on the Mitsubishi Heavy Industries Ac system. Check section
¡Error! No se
encuentra el origen de la referencia.
for more information.
Property Identifier
Property Datatype
Value
ASHRAE IBOX
Object_Identifier
BACnetObjectIdentifier
(Analog Output, 1)
R
R
Object_Name
CharacterString
“RoomTemperature_command”
R
R
Object_Type
BACnetObjectType
ANALOG_INPUT (0)
R
R
Present_Value
REAL
-
10…50
R
R
Description
CharacterString
-
O
-
Device_Type
CharacterString
-
O
-
Status_Flags
BACnetStatusFlags
{FALSE, FALSE, FALSE, FALSE}
R
R
Event_State
BACnetEventState
STATE_NORMAL (0)
R
R
Reliability
BACnetReliability
NO_FAULT_DETECTED (0)
O
R
Out_Of_Service
BOOLEAN
FALSE
R
R
Update_Interval
Unsigned
-
O
-
Units **
BACnetEngineeringUnits
Degrees Celsius (62)
Degrees Fahrenheit (64)
R
R
Min_Pres_Value
REAL
-
O
-
Max_Pres_Value
REAL
-
O
-
Resolution
REAL
-
O
-
COV_Increment
REAL
0
O
W
Priority_Array
BACnetPriorityArray
BACnetPriorityArray
R
R
Relinquish_Default
Unsigned
22
R
R
Time_Delay
Unsigned
-
O
-
Notification_Class
Unsigned
-
O
-
High_Limit
REAL
-
O
-
Low_Limit
REAL
-
O
-
Deadband
REAL
-
O
-
Limit_Enable
BACnetLimitEnable
-
O
-
Event_Enable
BACnetEventTransitionBits
-
O
-
Acked_Transitions
BACnetEventTransitionBits
-
O
-
Notify_Type
BACnetNotifyType
-
O
-
Event_Time_Stamps
BACnetArray[N] of
BACnetTimeStamp
-
O
-
Profile_Name
CharacterString
-
O
-
** Use of Celsius or Fahrenheits units can be selected throught the switch configuration. Check section 6.1 for more information.