KNX - Haier A.C. (VRF line) 

User's manual r1.0 EN 

 

 

© Intesis Software S.L.U. - All rights reserved  

This information is subject to change without notice

 

 

 

IntesisBox is a registred trademark of

 

Intesis Software SLU

 

 

 

URL 

email 

tel 

 

http://www.intesisbox.com                                          
[email protected] 
+34 938047134 

 

26 / 31 

7

 

Error Codes

 

 

Error Code 

in 

KNX Object 

Error in 

Remote 

Controller 

Category 

Error Name 

Indoor Unit 

Indoor ambient temp.sensor TA (Tas) failure 

Indoor gas pipe temp. sensor TC1 failure 

Indoor liquid pipe temp. sensor TC2 failure 

Dual heat source sensor TW failure 

Indoor EEPROM failure 

Communication between indoor and outdoor failure 

Communication between indoor and wired controller failure 

Indoor float switch failure 

Indoor address repeated failure 

10 

10 

Reserved 

11 

11 

Reserved 

12 

12 

No 50 Hz zero passage signal 

13 

13 

Coil sensor TC3 failure 

14 

14 

DC motor failure 

15 

15 

Indoor ambient temp.sensor TA (Taf) failure 

16 

16 

17 

17 

Outdoor Unit 

18 

18 

19 

19 

20 

20 

Defrosting temp. sensor Tdef1 failure 
Defrosting temp. sensor Tdef2 failure 

21 

21 

Ambient temp. sensor Ta failure 

22 

22 

Suction temp. sensor Ts1 failure 
Suction temp. sensor Ts2 failure 
Suction temp. sensor Tsacc failure 
Suction temp. sensor Tsuc failure 

23 

23 

Discharging temp. sensor Tdi failure 
Discharging temp. sensor Td1 failure 
Discharging temp. sensor Td2 failure 

24 

24 

Oil temp. sensor Toilp failure 
Oil temp. sensor Toil failure 

25 

25 

Inlet temp. of heat exchanger Toci1 failure 
Inlet temp. of heat exchanger Toci2 failure 

26 

26 

indoor communication failure 
Reduce the number of indoor units failure 

Increase the number of indoor units failure 

27 

27 

Oil temp. too high protection (Toil) 

Oil temp. too high protection (Toi2) 

28 

28 

High pressure sensor Pd1 failure 
High pressure sensor Pd2 failure 

29 

29 

Low pressure sensor Ps failure 

30 

30 

High pressure switch HPSi failure 
High pressure switch HPS1 failure 
High pressure switch HPS2 failure 

31 

31 

Liquid pipe pressure Pl failure 

32 

32 

Outlet temp. of subcooler Tsco failure 
Liquid pipe SC temp. of subcooler Tliqsc failure 

33 

33 

EEPROM (AT24C04) failure 

34 

34 

Discharging temp. too high protection (Tdi) 
Discharging temp. too high protection (Td1) 
Discharging temp. too high protection (Td2) 

35 

35 

4-way valve reversing failure 
4-way valve reversing failure 

36 

36 

Oil temp. too low protection (Toil) 
Oil temp. too low protection (Toi2) 

37 

37 

Lack of phase of 3N power supply or wrong phase sequence 

38 

38 

High pressure sensor Pd too low protection 

39 

39 

Low pressure sensor Ps too low protection 
Compression ratio too high protection 
Compression 1 ratio too low protection 
Compression 2 ratio too low protection 

40 

40 

High pressure sensor Pd1 too high protection 
High pressure sensor Pd2 too high protection 

41 

41 

Water temp. Twi too low protection 
Water temp. Twi too high protection 

42 

42 

Frost protection of water system 
Water system out of water freeze protection 
Water flow of Water system is too small to protect 

43 

43 

Discharging temp. sensor Tdi too low protection 
Discharging temp. sensor Td1 too low protection 
Discharging temp. sensor Td2 too low protection 

Summary of Contents for HA-AC-KNX-16

Page 1: ...IntesisBox KNX HA AC KNX 8 16 64 v1 0 User s Manual r1 eng Issue Date 11 2017...

Page 2: ...x is a registred trademark of Intesis Software SLU URL email tel http www intesisbox com info intesisbox com 34 938047134 2 31 Interface for integration of Haier air conditioners into KNX TP 1 EIB con...

Page 3: ...cument is furnished under a license agreement or nondisclosure agreement The software may be used only in accordance with the terms of those agreements No part of this publication may be reproduced st...

Page 4: ...nable use of object for Mode 12 4 2 4 Enable use of bit type Mode objects for control 12 4 2 5 Enable use of bit type Mode objects for status 13 4 2 6 Enable use of Text object for Mode 13 4 3 Global...

Page 5: ...on even inside the A C indoor unit Quick and non visible installation External power not required Direct connection to the KNX EIB bus Direct connection to the AC indoor unit Fully KNX interoperable c...

Page 6: ...oor unit s front cover again Connection of the interface to the KNX bus Disconnect power of the KNX bus Connect the interface to the KNX TP 1 EIB bus using the KNX standard connector red grey of the i...

Page 7: ...p www intesisbox com info intesisbox com 34 938047134 7 31 3 Configuration and setup This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS ETS project fo...

Page 8: ...r the first time the gateway shows the following default parameter configuration Figure 4 1 Default parameter configuration With this configuration it s possible to send On Off Control_ On Off change...

Page 9: ...re sending the programing the maximum number of AC units your device supports Figure 4 4 Parameter detail Select the version of the gateway that you have HA AC KNX 8 if you only want to control up to...

Page 10: ...Super Slow all status communication objects will send its value if needed but slower than in the previous option Slow Figure 4 7 Parameter detail 4 1 5 Enable object Error Code 2byte This parameter sh...

Page 11: ...is no error 4 2 Global mode configuration Figure 4 10 Default Mode Configuration dialog All the parameters in this section are related with the different mode properties and communication objects 3 2...

Page 12: ...lue 4 2 3 Enable use of object for Mode This parameter shows hides the Control_ Mode communication object which let s you change the indoor unit mode by using two different datapoint types 10 o If set...

Page 13: ...bit type Mode objects for status This parameter shows hides the bit type Status_ Mode objects 28 29 30 31 32 o If set to no the objects will not be shown o If set to yes the Status_ Mode objects for A...

Page 14: ...numerated DPT_5 010 can be selected o When Enumerated DPT 5 010 is selected Control_ Fan Speed and Status_ Fan Speed communication objects for this DPT will appear Also depending on the number of fan...

Page 15: ...hird one 4 3 2 Enable use of Fan Speed Man Auto objects for Control and Status This parameter shows hides the Control_ Fan Speed Man Auto and Status_ Fan Speed Man Auto communication object which lets...

Page 16: ...Auto mode and you want roll over to be enabled Auto S1 S2 SN Select this option if you have Auto mode and you don t want roll over to be enabled Auto S1 S2 SN Auto S1 Select this option if you have A...

Page 17: ...set to yes the Status_ Fan Speed objects for Speed 1 Speed 2 and Speed 3 if available will appear When a Fan Speed is enabled a 1 value is returned through its bit type object 4 3 6 Enable use of Tex...

Page 18: ...tion objects 4 4 1 Enable use of obj for Setpoint This parameter shows hides the Control_ Setpoint Temp communication object which lets you change the indoor unit setpoint temperature by using two dif...

Page 19: ...n example consider the following situation User wants 19 C KNX Setp Temp User sensor a KNX sensor reads 21 C KNX Amb Temp Ambient temp read by Haier system is 24 C Ambient Ref Temp In this example the...

Page 20: ...e objects for Control and Status This parameter shows hides the Control_ Control Mode and Status_ Control Mode communication objects which lets you change the indoor unit control No Central LIFO Last...

Page 21: ...ark of Intesis Software SLU URL email tel http www intesisbox com info intesisbox com 34 938047134 21 31 Figure 4 24 Parameter detail o If set to Apply same initial state to all Indoor Units the param...

Page 22: ...URL email tel http www intesisbox com info intesisbox com 34 938047134 22 31 4 6 Addressing of Indoor Units Figure 4 24 Parameter detail In this section you will be able to set the AC addressing for...

Page 23: ...without notice IntesisBox is a registred trademark of Intesis Software SLU URL email tel http www intesisbox com info intesisbox com 34 938047134 23 31 4 7 License Figure 4 24 Parameter detail Use thi...

Page 24: ...Power is supplied by 1 x KNX bus 29V DC 7mA Operational Humidity 90 RH non condensing Terminal Wiring for low voltage signals For terminal solid wires or stranded wires twisted or with ferrule 1 core...

Page 25: ...stred trademark of Intesis Software SLU URL email tel http www intesisbox com info intesisbox com 34 938047134 25 31 6 AC Unit Types compatibility A list of Haier indoor unit model references compatib...

Page 26: ...exchanger Toci1 failure Inlet temp of heat exchanger Toci2 failure 26 26 indoor communication failure Reduce the number of indoor units failure Increase the number of indoor units failure 27 27 Oil te...

Page 27: ...iving board failure 68 68 69 69 70 70 71 71 Left DC motor blocked Right DC motor blocked 72 72 Left DC motor reversed Right DC motor reversed 73 73 Left DC motor current too high Right DC motor curren...

Page 28: ...ilure Model 2 startup failure 119 119 Current Detecting Circuit Abnormal of transducer 1 Current Detecting Circuit Abnormal of transducer 2 120 120 Power supply of transducer 1 abnormal Power supply o...

Page 29: ...byte DPT_Scaling 5 001 W T 1 Auto 6 Control_ Mode Heat 1 byte DPT_Scaling 5 001 W T 1 Heat 7 Control_ Mode Cool 1 bit DPT_Bool 1 002 W T 1 Cool 8 Control_ Mode Fan 1 bit DPT_Bool 1 002 W T 1 Dry 9 Co...

Page 30: ...Bool 1 002 W T 1 Central Controller 23 Control_ Control Mode Lock 1 bit DPT_Bool 1 002 W T 1 Lock Central Controller On Off 24 Status_ On Off 1 bit DPT_Switch 1 001 R T 0 Off 1 On Mode 25 Status_ Oper...

Page 31: ...atus_ AC Ambient Ref Temp 2 byte DPT_Value_Temp 9 001 R T C value in EIS5 format Error 42 Status_ Error Alarm 1 bit DTP_Alarm 1 005 R T 0 No Alarm 1 Alarm 43 Status_ Error Code 2 byte Enumerated R T 0...

Reviews: