KNX - Haier A.C. (VRF line) 

User's manual r1.0 EN 

 

 

© Intesis Software S.L.U. - All rights reserved 

This information is subject to change without notice

 

 

IntesisBox

®

 

is a registered trademark of Intesis Software SLU

 

 

URL 
Email 
tel 

 

http://www.intesisbox.com                                          
[email protected] 
+34 938047134 

30 / 31 

 

 

Temperature 

17 

Control_ Setpoint Temperature 

2 byte 

DPT_Value_Temp 

9.001 

  

W  T     17ºC to 30ºC 

18 

Control_ Setpoint Temp +/- 

1 bit 

DPT_Step 

1.007 

  

W        0 - Decrease; 1 - Increase 

Control_ Setpoint Temp +/- 

1 bit 

DPT_UpDown 

1.008 

  

W        0 - Up; 1 - Down 

19 

Control_ Ambient Temperature 

2 byte 

DPT_Value_Temp 

9.001 

  

W  T     ºC value in EIS5 format 

Control Mode 

20 

Control_ Control Mode No Central 

1 bit 

DPT_Bool 

1.002 

  

W  T     1 

 No Central Controller 

21 

Control_ Control Mode LIFO 

1 bit 

DPT_Bool 

1.002 

 

W  T 

  1 

 Last Input First Output (LIFO) 

22 

Control_ Control Mode Central 

1 bit 

DPT_Bool 

1.002 

 

W  T 

  1 

 Central Controller 

23 

Control_ Control Mode Lock 

1 bit 

DPT_Bool 

1.002 

 

W  T 

  1 

 Lock Central Controller 

 
 
 

On/Off 

24 

Status_ On/Off 

1 bit 

DPT_Switch 

1.001 

   T     0 - Off; 1-On 

Mode 

25 

Status_ Operating Mode 

1 byte 

DPT_HVACMode 

20.102 

 

T     0 - Auto; 1 - Com; 2 - Stan; 3 - Eco; 4 

 Pro 

26 

Status_ Mode 

1 byte  DPT_HVACContrMode  20.105 

   T     0 - Auto; 1 - Heat; 3 - Cool; 9 - Fan; 14 - Dry 

27 

Status_ Mode Cool/Heat 

1 bit 

DPT_Heat/Cool 

1.100 

   T     0 - Cool; 1 - Heat 

28 

Status_ Mode Auto 

1 bit 

DPT_Bool 

1.002 

   T     1 - Auto 

29 

Status_ Mode Heat 

1 bit 

DPT_Bool 

1.002 

   T     1 - Heat 

30 

Status_ Mode Cool 

1 bit 

DPT_Bool 

1.002 

   T     1 - Cool 

31 

Status_ Mode Fan 

1 bit 

DPT_Bool 

1.002 

   T     1 - Fan 

32 

Status_ Mode Dry 

1 bit 

DPT_Bool 

1.002 

   T     1 - Dry 

33 

Status_ Mode Text 

14 byte 

DPT_String_8859_1 

16.001 

   T     ASCII String 

Fan Speed 

34 

Status_ Fan Speed / 3 Speeds 

1 byte 

DPT_Scaling 

5.001 

   T     33% - Speed 1; 67% - Speed 2; 100% - Speed 3 

Status_ Fan Speed / 3 Speeds 

1 byte 

DPT_Enumerated 

5.010 

   T     1 - Speed 1; 2 - Speed 2; 3 - Speed 3 

35 

Status_ Fan Speed Man/Auto 

1 bit 

DPT_Bool 

1.002 

   T     0 

 Manual; 1 

 Auto 

Summary of Contents for HA-AC-KNX-16

Page 1: ...IntesisBox KNX HA AC KNX 8 16 64 v1 0 User s Manual r1 eng Issue Date 11 2017...

Page 2: ...x is a registred trademark of Intesis Software SLU URL email tel http www intesisbox com info intesisbox com 34 938047134 2 31 Interface for integration of Haier air conditioners into KNX TP 1 EIB con...

Page 3: ...cument is furnished under a license agreement or nondisclosure agreement The software may be used only in accordance with the terms of those agreements No part of this publication may be reproduced st...

Page 4: ...nable use of object for Mode 12 4 2 4 Enable use of bit type Mode objects for control 12 4 2 5 Enable use of bit type Mode objects for status 13 4 2 6 Enable use of Text object for Mode 13 4 3 Global...

Page 5: ...on even inside the A C indoor unit Quick and non visible installation External power not required Direct connection to the KNX EIB bus Direct connection to the AC indoor unit Fully KNX interoperable c...

Page 6: ...oor unit s front cover again Connection of the interface to the KNX bus Disconnect power of the KNX bus Connect the interface to the KNX TP 1 EIB bus using the KNX standard connector red grey of the i...

Page 7: ...p www intesisbox com info intesisbox com 34 938047134 7 31 3 Configuration and setup This is a fully compatible KNX device which must be configured and setup using standard KNX tool ETS ETS project fo...

Page 8: ...r the first time the gateway shows the following default parameter configuration Figure 4 1 Default parameter configuration With this configuration it s possible to send On Off Control_ On Off change...

Page 9: ...re sending the programing the maximum number of AC units your device supports Figure 4 4 Parameter detail Select the version of the gateway that you have HA AC KNX 8 if you only want to control up to...

Page 10: ...Super Slow all status communication objects will send its value if needed but slower than in the previous option Slow Figure 4 7 Parameter detail 4 1 5 Enable object Error Code 2byte This parameter sh...

Page 11: ...is no error 4 2 Global mode configuration Figure 4 10 Default Mode Configuration dialog All the parameters in this section are related with the different mode properties and communication objects 3 2...

Page 12: ...lue 4 2 3 Enable use of object for Mode This parameter shows hides the Control_ Mode communication object which let s you change the indoor unit mode by using two different datapoint types 10 o If set...

Page 13: ...bit type Mode objects for status This parameter shows hides the bit type Status_ Mode objects 28 29 30 31 32 o If set to no the objects will not be shown o If set to yes the Status_ Mode objects for A...

Page 14: ...numerated DPT_5 010 can be selected o When Enumerated DPT 5 010 is selected Control_ Fan Speed and Status_ Fan Speed communication objects for this DPT will appear Also depending on the number of fan...

Page 15: ...hird one 4 3 2 Enable use of Fan Speed Man Auto objects for Control and Status This parameter shows hides the Control_ Fan Speed Man Auto and Status_ Fan Speed Man Auto communication object which lets...

Page 16: ...Auto mode and you want roll over to be enabled Auto S1 S2 SN Select this option if you have Auto mode and you don t want roll over to be enabled Auto S1 S2 SN Auto S1 Select this option if you have A...

Page 17: ...set to yes the Status_ Fan Speed objects for Speed 1 Speed 2 and Speed 3 if available will appear When a Fan Speed is enabled a 1 value is returned through its bit type object 4 3 6 Enable use of Tex...

Page 18: ...tion objects 4 4 1 Enable use of obj for Setpoint This parameter shows hides the Control_ Setpoint Temp communication object which lets you change the indoor unit setpoint temperature by using two dif...

Page 19: ...n example consider the following situation User wants 19 C KNX Setp Temp User sensor a KNX sensor reads 21 C KNX Amb Temp Ambient temp read by Haier system is 24 C Ambient Ref Temp In this example the...

Page 20: ...e objects for Control and Status This parameter shows hides the Control_ Control Mode and Status_ Control Mode communication objects which lets you change the indoor unit control No Central LIFO Last...

Page 21: ...ark of Intesis Software SLU URL email tel http www intesisbox com info intesisbox com 34 938047134 21 31 Figure 4 24 Parameter detail o If set to Apply same initial state to all Indoor Units the param...

Page 22: ...URL email tel http www intesisbox com info intesisbox com 34 938047134 22 31 4 6 Addressing of Indoor Units Figure 4 24 Parameter detail In this section you will be able to set the AC addressing for...

Page 23: ...without notice IntesisBox is a registred trademark of Intesis Software SLU URL email tel http www intesisbox com info intesisbox com 34 938047134 23 31 4 7 License Figure 4 24 Parameter detail Use thi...

Page 24: ...Power is supplied by 1 x KNX bus 29V DC 7mA Operational Humidity 90 RH non condensing Terminal Wiring for low voltage signals For terminal solid wires or stranded wires twisted or with ferrule 1 core...

Page 25: ...stred trademark of Intesis Software SLU URL email tel http www intesisbox com info intesisbox com 34 938047134 25 31 6 AC Unit Types compatibility A list of Haier indoor unit model references compatib...

Page 26: ...exchanger Toci1 failure Inlet temp of heat exchanger Toci2 failure 26 26 indoor communication failure Reduce the number of indoor units failure Increase the number of indoor units failure 27 27 Oil te...

Page 27: ...iving board failure 68 68 69 69 70 70 71 71 Left DC motor blocked Right DC motor blocked 72 72 Left DC motor reversed Right DC motor reversed 73 73 Left DC motor current too high Right DC motor curren...

Page 28: ...ilure Model 2 startup failure 119 119 Current Detecting Circuit Abnormal of transducer 1 Current Detecting Circuit Abnormal of transducer 2 120 120 Power supply of transducer 1 abnormal Power supply o...

Page 29: ...byte DPT_Scaling 5 001 W T 1 Auto 6 Control_ Mode Heat 1 byte DPT_Scaling 5 001 W T 1 Heat 7 Control_ Mode Cool 1 bit DPT_Bool 1 002 W T 1 Cool 8 Control_ Mode Fan 1 bit DPT_Bool 1 002 W T 1 Dry 9 Co...

Page 30: ...Bool 1 002 W T 1 Central Controller 23 Control_ Control Mode Lock 1 bit DPT_Bool 1 002 W T 1 Lock Central Controller On Off 24 Status_ On Off 1 bit DPT_Switch 1 001 R T 0 Off 1 On Mode 25 Status_ Oper...

Page 31: ...atus_ AC Ambient Ref Temp 2 byte DPT_Value_Temp 9 001 R T C value in EIS5 format Error 42 Status_ Error Alarm 1 bit DTP_Alarm 1 005 R T 0 No Alarm 1 Alarm 43 Status_ Error Code 2 byte Enumerated R T 0...

Reviews: