Temperature
17
Control_ Setpoint Temperature
2 byte
DPT_Value_Temp
9.001
W T 17ºC to 30ºC
18
Control_ Setpoint Temp +/-
1 bit
DPT_Step
1.007
W 0 - Decrease; 1 - Increase
Control_ Setpoint Temp +/-
1 bit
DPT_UpDown
1.008
W 0 - Up; 1 - Down
19
Control_ Ambient Temperature
2 byte
DPT_Value_Temp
9.001
W T ºC value in EIS5 format
Control Mode
20
Control_ Control Mode No Central
1 bit
DPT_Bool
1.002
W T 1
–
No Central Controller
21
Control_ Control Mode LIFO
1 bit
DPT_Bool
1.002
W T
1
–
Last Input First Output (LIFO)
22
Control_ Control Mode Central
1 bit
DPT_Bool
1.002
W T
1
–
Central Controller
23
Control_ Control Mode Lock
1 bit
DPT_Bool
1.002
W T
1
–
Lock Central Controller
On/Off
24
Status_ On/Off
1 bit
DPT_Switch
1.001
R
T 0 - Off; 1-On
Mode
25
Status_ Operating Mode
1 byte
DPT_HVACMode
20.102
R
T 0 - Auto; 1 - Com; 2 - Stan; 3 - Eco; 4
–
Pro
26
Status_ Mode
1 byte DPT_HVACContrMode 20.105
R
T 0 - Auto; 1 - Heat; 3 - Cool; 9 - Fan; 14 - Dry
27
Status_ Mode Cool/Heat
1 bit
DPT_Heat/Cool
1.100
R
T 0 - Cool; 1 - Heat
28
Status_ Mode Auto
1 bit
DPT_Bool
1.002
R
T 1 - Auto
29
Status_ Mode Heat
1 bit
DPT_Bool
1.002
R
T 1 - Heat
30
Status_ Mode Cool
1 bit
DPT_Bool
1.002
R
T 1 - Cool
31
Status_ Mode Fan
1 bit
DPT_Bool
1.002
R
T 1 - Fan
32
Status_ Mode Dry
1 bit
DPT_Bool
1.002
R
T 1 - Dry
33
Status_ Mode Text
14 byte
DPT_String_8859_1
16.001
R
T ASCII String
Fan Speed
34
Status_ Fan Speed / 3 Speeds
1 byte
DPT_Scaling
5.001
R
T 33% - Speed 1; 67% - Speed 2; 100% - Speed 3
Status_ Fan Speed / 3 Speeds
1 byte
DPT_Enumerated
5.010
R
T 1 - Speed 1; 2 - Speed 2; 3 - Speed 3
35
Status_ Fan Speed Man/Auto
1 bit
DPT_Bool
1.002
R
T 0
–
Manual; 1
–
Auto