This object can be read and also sends the indoor unit error, if occurred, in text
format. The errors shown have the same format as in the remote controller and in
the error list from the indoor unit manufacturer. If the object’s value is empty
,
that means there is no error.
4.2
Global mode configuration
Figure 4.10
Default Mode Configuration dialog
All the parameters in this section are related with the different mode properties and
communication objects.
3:
26:
The byte-type communication object for Mode works with the DTP_20.105. Auto mode will be
enabled with a
“0”
value, Heat mode with a
“1”
value, Cool mode with a
“3”
value, Fan mode
with a
“9”
value and Dry mode with a
“14”
value.
4.2.1
Enable use of “Operating Mode” objects
This parameter shows/hides the
Control_
and
Status_ Mode Operating Mode
communication
objects.
2:
25:
4.2.2
Enable use of Mode Heat/Cool objects
This parameter shows/hides the
Control_
and
Status_ Mode Cool/Heat
communication objects.
4:
27:
o
If set to
“
Disabled
”
the objects will not be shown.