KNX - Haier A.C. (VRF line)
User's manual r1.0 EN
© Intesis Software S.L.U. - All rights reserved
This information is subject to change without notice
IntesisBox
®
is a registered trademark of Intesis Software SLU
URL
Email
tel
http://www.intesisbox.com
[email protected]
+34 938047134
31 / 31
36
Status_ Fan Speed 1
1 bit
DPT_Bool
1.002
R
T 1 - Speed 1
37
Status_ Fan Speed 2
1 bit
DPT_Bool
1.002
R
T 1 - Speed 2
38
Status_ Fan Speed 3
1 bit
DPT_Bool
1.002
R
T 1 - Speed 3
39
Status_ Fan Speed Text
14 byte
DPT_String_8859_1
16.001
R
T ASCII String
Temperature
40
Status_ AC Setpoint Temp
2 byte
DPT_Value_Temp
9.001
R
T 16ºC to 32ºC
41
Status_ AC Ambient Ref Temp
2 byte
DPT_Value_Temp
9.001
R
T ºC value in EIS5 format
Error
42
Status_ Error/Alarm
1 bit
DTP_Alarm
1.005
R
T 0 - No Alarm; 1 - Alarm
43
Status_ Error Code
2 byte
Enumerated
R
T 0 - No Error; Any other see user's manual
44
Status_ Error Text code
14 byte
DPT_String_8859_1
16.001
R
T 2 char Haier Error; Empty - none
Control Mode
45
Control_ Control Mode No Central
1 bit
DPT_Bool
1.002
W T 1
–
No Central Controller
46
Control_ Control Mode LIFO
1 bit
DPT_Bool
1.002
W T
1
–
Last Input First Output (LIFO)
47
Control_ Control Mode Central
1 bit
DPT_Bool
1.002
W T
1
–
Central Controller
48
Control_ Control Mode Lock
1 bit
DPT_Bool
1.002
W T
1
–
Lock Central Controller
NOTE:
This addressing corresponds to the first AC indoor unit of the configuration. Communication objects for the rest of AC units are
consecutively listed.