Take care that the NTC is positioned in free air far from the 
heat sink or any other component. Its function is to measure 
the batteries working temperature inside the cabinet. The 
following table should be taken into account to measure the 
charge voltage. 

• 

15°C: 13.74 V

 

• 

20°C: 13.65 V

 

• 

25°C: 13.56 V

 

• 

30°C: 13.46 V

 

• 

35°C: 13.37 V

 

Measure the voltage at the battery terminal (Batt + and 

−) with 

no battery attached. 

Cabling ATS1203(N)/ATS1204(N) 

Note: 

Preferred system databus wiring 

— see Figure 4. Refer 

to the ATS control panel installation guide for a more detailed 
description of the cabling. 

The “TERM” link is on the first and last devices on the system 
databus. In a “star” wiring configuration, the “TERM” link is only 
fitted on the devices at the ends of the two longest system 
databus cable runs.  

Figure 4: System databus wiring 

(1)  TERM link fitted (first device on local databus). 
(2)  ATS control panel. 
(3)  ATS1105 LCD RAS (TERM switch not set to ON). 
(4)  Separate 12 V power supply. (Required if RAS is more than 

100 

m from the nearest panel or DGP. Connect “−” to “−” of the 

databus). 

(5)  Preferred data cable type is WCAT 52 (2 pair twisted). 
(6)  TERM link fitted (last device on local databus).  
(7)  Earth connection to connect shield [1]. 
(8)  Any data gathering panel like ATS1201, ATS1203, ATS1204, 

ATS1210, ATS1220 or ATS125x. 

[1]  Connect cable shield to one device only. 

See 

“System databus connection” below and “Earthing” below. 

ATS1203(N)/ATS1204(N) connections 

Figure 5: ATS1203(N)/ATS1204(N) connections 

(1)  12 V battery 
(2)  System earth  
(3)  AC connection from 

transformer 

(4)  Dipswitch to set DGP 

address 

(5)  Battery load resistor jumper. 
(6)  Earth connection for cable 

screens (shields) 

(7)  AC connection from 

transformer and battery 
power 

(8)  Clock-out Interface to plug 

on output expansion or 4-
way non-clocked output 
expansion (e.g. ATS1810). 

(9)  Link to 12 VDC to 

output board 

(10)  Auxiliary power supply 

output 

(11)  Link to terminate databus 

 

(12)  Interface to ATS1202 input 

expanders 

(13)  RS485 system databus & 

box tamper connections 

(14)  Zones 
(15)  External siren 
(16)  System databus  
(17)  Normally closed pry-off 

tamper contact 

(18)  Normally closed tamper 

contact 

(19) 

1 kΩ resistor must be fitted 
if external siren not 
connected 

(20)  Normally closed panel 

housing tamper contact 

(21)  Normally closed alarm 

contact 

(22) 

External 8Ω siren speaker 
or siren 

Notes 

• 

If the battery load resistor is enabled, output 8 is no longer 
available for non-clocked output expansion boards. 

• 

The battery load resistor setting must correspond with 
DGP programmed settings. See 

“Menu 3, DGP settings” 

on page 7 for details. 

• 

In case the DGP is set for 2 DGPs to enable all 32 
outputs, the control panel programming should be set up 
to poll the DGP address and the a 1. 

Links 

• 

TERM: Termination of databus. Only to be used on first 
and last device on the local databus. 

• 

+12V: C12 VDC to output board. 

DGP DIP switch settings 

See Figure 2. 

Address: Select DGP address. Set switches 1 to 4 to OFF to 
disable the DGP (see Figure 2 for correct address settings). 

LEDs 

• 

Tx: Red LED flashes when remote units (RAS and DGP) 
are replying to polling. 

• 

Rx: Yellow LED flashes when panel is polling remote 
units. It must always be active. 

System databus connection 

The system databus is used to connect Data Gathering Panels 
(to provide extra zones) and Arming Stations to the ATS 
control panel. Remote devices can be up to 1.5 km from an 
ATS control panel. 

Arming Stations and Data Gathering Panels must be 
connected via a 2 pair twisted shielded data cable from the 
system databus connection. (WCAT 52 is recommended). 

The shield of the data cable should be connected to earth at 
the ATS control panel or any other earth point. However it 
should be left disconnected at the other end. 

It is recommended that where the distance between the arming 
station and the nearest device is more than 100 meters, a 
separate power supply be used to power the arming station. 

To power the arming station, do not connect “+” from the 
system databus. Connect “+” of the local power supply to “+” 
on the arming station and connect 0 volts from the power 
supply and 0 volts from the system databus to the arming 
station terminal marked “−”. 

See also 

“Cabling ATS1203(N)/ATS1204(N)” above. 

Earthing 

See Figure 3. 

WARNING: 

Correct earthing procedures must be followed. 

Earthing of one cabinet containing several devices 

All devices designed for the system have earth connections via 
metal studs to the metal housing. Take care, that these metal 
studs make good connection to the housing (beware of paint). 

Summary of Contents for ATS1203(N)

Page 1: ...Inc 1 24 P N 1064130 ML REV E ISS 01JUL19 ATS1203 N ATS1204 N 8 to 32 Zone DGP with 3A Power Supply Installation Sheet EN DE FR IT 1 2 3 1 2 3 3 4 5 6 1740 ATS1201 1740 ATS CP ATS1210 ATS1116 ATS1203...

Page 2: ...2 24 P N 1064130 ML REV E ISS 01JUL19 4 7 2 7 1 5 4 3 6 8 8 4 5 3 1 2 6...

Page 3: ...x 3 A total Both the mains power supply and the battery are monitored The DGP also provides for 8 to 32 outputs occupying 2 DGP addresses when selected to support more than 16 outputs The ATS1203 N AT...

Page 4: ...l applicable standard Only a qualified electrician or other suitable trained and qualified person should attempt to wire this system to the mains or to the public telephone network Ensure that there i...

Page 5: ...istor must be fitted if external siren not connected 20 Normally closed panel housing tamper contact 21 Normally closed alarm contact 22 External 8 siren speaker or siren Notes If the battery load res...

Page 6: ...e If the battery load test resistor is enabled output 8 follows the battery test except when using clocked output devices Zone numbering The ATS1203 N ATS1204 N has 8 zones that can be expanded using...

Page 7: ...tion at 230V 360 mA Main board supply voltage 23 VAC typical Power supply specifications Power supply voltage 13 8 VDC 5 Power supply current 2 9 A max at 13 8 VDC 5 Auxiliary Power output J14 13 8 VD...

Page 8: ...llen muss der Anschluss an die Stromversorgung mit den lokalen Regelungen bereinstimmen WARNUNG Gefahr von Stromschl gen Entfernen Sie vor der Installation oder Entfernung von Ger ten alle Energiequel...

Page 9: ...er geeigneten Brandschutzklasse HB oder besser entspricht Alle Komponenten die entweder direkt an den Relaiskontakten der Erweiterung oder ber ein externes Relais von den Transistor Schaltausg ngen de...

Page 10: ...werden dass sie die AME Adresse und die AME Adresse 1 abfragt Steckbr cken TERM Abschluss des Datenbusses Wird nur am ersten und letzten Ger t im lokalen Datenbus verwendet 12V 12 V Gleichspannung mi...

Page 11: ...n Die ATS1203 N ATS1204 N k nnen auch 32 Ausg nge unterst tzen Dies k nnen Sie aktivieren indem Sie im Men 3 AME Einstellungen die erste Option 2 AME Adressen Erweiteret AME ausw hlen Denken Sie daran...

Page 12: ...des Batterie Lastwiderstands entsprechen Abbildung 5 Punkt 5 3 Netzpr fung Aktiviert deaktiviert die Netzpr fung Stellen Sie die Pr fung aus wenn keine Netzversorgung verwendet wird um zu verhindern...

Page 13: ...der 2014 35 EU entspricht F r weitere Informationen siehe www utcfireandsecurity com oder www interlogix com 2012 19 EU WEEE Produkte die mit diesem Symbol gekennzeichnet sind d rfen nicht als unsorti...

Page 14: ...s par es Si les entr es de c bles sup rieures ou inf rieures sont utilis es pour passer des c bles utiliser des presses toupes adapt s et conformes la classe de flammabilit HB minimum Le raccordement...

Page 15: ...ouverture normalement ferm 21 Contact d alarme normalement ferm 22 Haut parleur de sir ne externe 8 ohm ou sir ne Notes Si la r sistance de charge batterie est activ e la 4 me sortie de la deuxi me c...

Page 16: ...n choisissant 2 DGP addresses dans le menu 3 DGP settings premi re option du menu avanc 28 vers autres modules Ne pas oublier de faire scruter les 2 DGPs par la centrale Note Lorsque la r sistance de...

Page 17: ...limentation Alimentation secteur principale J17 AC 230 VAC 10 50 Hz 10 Consommation 230V 360 mA Alimentation secondaire de la carte m re 23 VAC nominal Donn es techniques chargeur Tension de sortie au...

Page 18: ...sti possibile utilizzare una connessione fissa oppure una connessione amovibile prelevata da una presa di corrente di rete con messa a terra Se si utilizza un cavo fisso inserire un interruttore bipol...

Page 19: ...sse di infiammabilit Classe HB o superiore Ogni circuito collegato ai contatti dei rel a bordo della centrale o rel esterni o alle uscite elettroniche deve essere a funzionamento in bassa tensione tip...

Page 20: ...deve essere impostata l interrogazione dell indirizzo del DGP E anche l indirizzo successivo 1 Links TERM Terminazione del bus Usare solamente sul primo e ultimo dispositivo sul bus locale 12V Connet...

Page 21: ...Nota Se il test della batteria abilitato l 8 uscita seguir il test batteria tranne se si utilizzano moduli multiplexati Numerazione zone L ATS1203 N ATS1204 N ha 8 zone che possono essere espanse usa...

Page 22: ...azioni di fabbrica Specifiche tecniche Specifiche alimentazione apparato Alimentazione principale J17 AC 230V 10 50 Hz 10 Consumo di corrente a 230 V 360 mA Alimentazione scheda elettronica 23V tipica...

Page 23: ...PER LA PROTEZIONE ANTINCENDIO Per ulteriori informazioni sulle esclusioni di garanzia e sulla sicurezza dei prodotti consultare il sito https firesecurityproducts com policy product warning oppure es...

Page 24: ...24 24 P N 1064130 ML REV E ISS 01JUL19...

Reviews: