The earth connections of every piece of equipment in the 
system can be used for connecting the shielding of shielded 
cables. However: never connect the shield at both sides to 
earth. If a device is placed in a plastic housing the earth lug of 
this device does not have to be connected. 

Earthing panels in a single building 

In one building several cabinets or devices are earthen to 
safety ground. 

The safety earth of this building has to be checked by a 
licensed contractor. 

Earthing panels in more buildings 

If the wiring extends to separate buildings, more than one 
common earth system will be used. Use isolator/repeaters 
ATS1740 to isolate the system databus. In this way the system 
is protected against variations in earth potential. 

Shielding 

The shielding of all shielded cables used in the system should 
only be connected at ONE side to one common earthing point 
in a building (see Figure 3). If a shielded databus cable is 
routed via more than one plastic device the shielding from 
incoming and outgoing cable has to be connected. 

Figure 3: System shielding example 

(1)  Building 1 
(2)  Building 2 
(3)  Mains power with local 

earth 

(4)  Earth lug 
(5)  Mains power connector

 

 

(6)  Advisor Master control 

panel 

(7)  System databus 
(8)  Device in plastic housing 
(9)  Device in metal housing

 

Connecting the data gathering panel to a 
control panel 

Refer to the Advisor Master installation guide for instructions. 

Zone and output numbering 

 

Control panel 

– 16 

 

DGP8 

129 

– 144 

DGP1 

17 

– 32 

 

DGP9 

145 

– 160 

DGP2 

33 

– 48 

 

DGP10 

161 

– 176 

DGP3 

49 

– 64 

 

DGP11 

177 

– 192 

DGP4 

65 

– 80 

 

DGP12 

193 

– 208 

DGP5 

81 

– 96 

 

DGP13 

209 

– 224 

DGP6 

97 

– 112 

 

DGP14 

225 

– 240 

DGP7 

113 

– 128 

 

DGP15 

241 

– 256 

 

Output numbering 

A DGP can have a maximum of 16 outputs available as relays 
or open collector outputs. The output numbers are the same as 
the 16 zone numbers allocated to the DGP address. 

The ATS1203(N)/ATS1204(N) can also support 32 outputs. 
Enable this by selecting “2 DGP addresses” in menu 3 – “DGP 
settings” (first option). Be aware that the ATS Control Panel 
needs to be setup to poll both DGP addresses. 

Note: 

If the battery load test resistor is enabled, output 8 

follows the battery test (except when using clocked output 
devices). 

Zone numbering 

The ATS1203(N)/ATS1204(N) has 8 zones that can be 
expanded using the ATS 1202 (8 zones) to a maximum of 
32 zones. If the number of zones exceeds 16, then the zones 
are taken from the next DGP address and DGP ceases to 
exist. 

For example, DGP 1 has 24 zones (zones 17 to 40). The next 
DGP in the system must now be addressed and polled as 
DGP 3, because zones 33 to 40 on DGP 1 have been taken 
from DGP 2. 

The unused zone numbers in the system (zones 41 to 48) 
must be programmed in the zone database as Type 0. 

Programming the DGP 

1.  Polling the ATS1203(N)/ATS1204(N). 

a. Enter menu 4 of the control panel installer menu, and 
add the address for the device, then press ENTER. 

b. Press ENTER, select the “DGP address” and press 
ENTER again to enter the DGP details. 

c. Select the device type 5 (ADVANCED DGP). 

d. Press ENTER until you are back to the main menu. 

Note: 

For more information on control panel programming, 

see 

Advisor Master Programming Manual

2.  The ATS1203(N)/ATS1204(N) provides a menu through 

which a number of options can be set. In addition the 
status of the ATS1203(N)/ATS1204(N) itself or inputs can 
be viewed. See Figure 6. 

To enter the programming menu for the 
ATS1203(N)/ATS1204(N): 

a. Enter menu 28 of the control panel installer menu.  

b. Press 1 ENTER followed by the DGP address selected 
and ENTER to enter the DGP menu. The display now 
shows “ATS1203” followed by the version number.  

c. Press ENTER to proceed to the menu or press the 
menu number followed by ENTER to go to a menu item 
directly. 

Menu 1, DGP status 

This menu lists different types of information regarding 
settings, DGP addresses to poll, inputs ranges, output ranges, 
current consumption, etc. To view all data, enter the menu and 
press ENTER to view the next item. 

Menu 2, Input status 

Shows the current status of all inputs that have been enabled 
and the digital value of the status. The range that is available 
can be viewed in the DGP Status. The input numbers used are 
related to the address selected. See “Zone and output 
numbering”. 

To view the status, enter the first input to view. The selected 
input status is shown. Press MENU to view the previous or 
ENTER to view the next input. 

Summary of Contents for ATS1203(N)

Page 1: ...Inc 1 24 P N 1064130 ML REV E ISS 01JUL19 ATS1203 N ATS1204 N 8 to 32 Zone DGP with 3A Power Supply Installation Sheet EN DE FR IT 1 2 3 1 2 3 3 4 5 6 1740 ATS1201 1740 ATS CP ATS1210 ATS1116 ATS1203...

Page 2: ...2 24 P N 1064130 ML REV E ISS 01JUL19 4 7 2 7 1 5 4 3 6 8 8 4 5 3 1 2 6...

Page 3: ...x 3 A total Both the mains power supply and the battery are monitored The DGP also provides for 8 to 32 outputs occupying 2 DGP addresses when selected to support more than 16 outputs The ATS1203 N AT...

Page 4: ...l applicable standard Only a qualified electrician or other suitable trained and qualified person should attempt to wire this system to the mains or to the public telephone network Ensure that there i...

Page 5: ...istor must be fitted if external siren not connected 20 Normally closed panel housing tamper contact 21 Normally closed alarm contact 22 External 8 siren speaker or siren Notes If the battery load res...

Page 6: ...e If the battery load test resistor is enabled output 8 follows the battery test except when using clocked output devices Zone numbering The ATS1203 N ATS1204 N has 8 zones that can be expanded using...

Page 7: ...tion at 230V 360 mA Main board supply voltage 23 VAC typical Power supply specifications Power supply voltage 13 8 VDC 5 Power supply current 2 9 A max at 13 8 VDC 5 Auxiliary Power output J14 13 8 VD...

Page 8: ...llen muss der Anschluss an die Stromversorgung mit den lokalen Regelungen bereinstimmen WARNUNG Gefahr von Stromschl gen Entfernen Sie vor der Installation oder Entfernung von Ger ten alle Energiequel...

Page 9: ...er geeigneten Brandschutzklasse HB oder besser entspricht Alle Komponenten die entweder direkt an den Relaiskontakten der Erweiterung oder ber ein externes Relais von den Transistor Schaltausg ngen de...

Page 10: ...werden dass sie die AME Adresse und die AME Adresse 1 abfragt Steckbr cken TERM Abschluss des Datenbusses Wird nur am ersten und letzten Ger t im lokalen Datenbus verwendet 12V 12 V Gleichspannung mi...

Page 11: ...n Die ATS1203 N ATS1204 N k nnen auch 32 Ausg nge unterst tzen Dies k nnen Sie aktivieren indem Sie im Men 3 AME Einstellungen die erste Option 2 AME Adressen Erweiteret AME ausw hlen Denken Sie daran...

Page 12: ...des Batterie Lastwiderstands entsprechen Abbildung 5 Punkt 5 3 Netzpr fung Aktiviert deaktiviert die Netzpr fung Stellen Sie die Pr fung aus wenn keine Netzversorgung verwendet wird um zu verhindern...

Page 13: ...der 2014 35 EU entspricht F r weitere Informationen siehe www utcfireandsecurity com oder www interlogix com 2012 19 EU WEEE Produkte die mit diesem Symbol gekennzeichnet sind d rfen nicht als unsorti...

Page 14: ...s par es Si les entr es de c bles sup rieures ou inf rieures sont utilis es pour passer des c bles utiliser des presses toupes adapt s et conformes la classe de flammabilit HB minimum Le raccordement...

Page 15: ...ouverture normalement ferm 21 Contact d alarme normalement ferm 22 Haut parleur de sir ne externe 8 ohm ou sir ne Notes Si la r sistance de charge batterie est activ e la 4 me sortie de la deuxi me c...

Page 16: ...n choisissant 2 DGP addresses dans le menu 3 DGP settings premi re option du menu avanc 28 vers autres modules Ne pas oublier de faire scruter les 2 DGPs par la centrale Note Lorsque la r sistance de...

Page 17: ...limentation Alimentation secteur principale J17 AC 230 VAC 10 50 Hz 10 Consommation 230V 360 mA Alimentation secondaire de la carte m re 23 VAC nominal Donn es techniques chargeur Tension de sortie au...

Page 18: ...sti possibile utilizzare una connessione fissa oppure una connessione amovibile prelevata da una presa di corrente di rete con messa a terra Se si utilizza un cavo fisso inserire un interruttore bipol...

Page 19: ...sse di infiammabilit Classe HB o superiore Ogni circuito collegato ai contatti dei rel a bordo della centrale o rel esterni o alle uscite elettroniche deve essere a funzionamento in bassa tensione tip...

Page 20: ...deve essere impostata l interrogazione dell indirizzo del DGP E anche l indirizzo successivo 1 Links TERM Terminazione del bus Usare solamente sul primo e ultimo dispositivo sul bus locale 12V Connet...

Page 21: ...Nota Se il test della batteria abilitato l 8 uscita seguir il test batteria tranne se si utilizzano moduli multiplexati Numerazione zone L ATS1203 N ATS1204 N ha 8 zone che possono essere espanse usa...

Page 22: ...azioni di fabbrica Specifiche tecniche Specifiche alimentazione apparato Alimentazione principale J17 AC 230V 10 50 Hz 10 Consumo di corrente a 230 V 360 mA Alimentazione scheda elettronica 23V tipica...

Page 23: ...PER LA PROTEZIONE ANTINCENDIO Per ulteriori informazioni sulle esclusioni di garanzia e sulla sicurezza dei prodotti consultare il sito https firesecurityproducts com policy product warning oppure es...

Page 24: ...24 24 P N 1064130 ML REV E ISS 01JUL19...

Reviews: