Interlogix ATS1203(N) Installation Sheet Download Page 7

 

P/N 1064130 (ML) • REV E • ISS 01JUL19 

 

7 / 24 

Menu 3, DGP settings 

Menu 3 provides for some additional settings related directly to 
the DGP functionality. Use the MENU key to change the 
settings. Use ENTER to accept the settings and move to the 
next item. 

1. DGP configuration

: selects the number of inputs and 

outputs used. Available settings:  

• 

1 DGP Address: Allows for max 16 inputs/outputs to be 
connected. Shows as “DGP: n” where n is the selected 
DGP address in menu 1, DGP status (Default setting) 

• 

1 DGP+exp: Allows for max 32 inputs/16 outputs to be 
connected. Shows as “DGP: n + exp” where n is the 
selected DGP address in menu 1, DGP status. 

• 

2 DGP Addresses: Allows for max 32 inputs/outputs to be 
connected but requires DGP polling to be enabled for the 
DGP address and the DGP a 1. Shows as “DGP: 
n + m” where n is the selected DGP address and m is the 
a 1 in menu 1, DGP status. 

2. Battery load: 

Select if the battery load resistor should be 

enabled on output 8. It will follow the battery test and add an 
additional 68 

Ω during the test. This option is required for 

regulations (SKAFOR). Default is OFF. 

Note: 

The setting must correspond with position of the battery 

load resistor jumper (Figure 5, item 5). 

3. Mains check: 

Enable/disable mains check. Set to OFF in 

case no mains power supply is used to avoid mains fail being 
reported. Default is ON. 

4. Extended mode: 

To enable anti-mask detection it is 

necessary to select Extended mode. Standard mode is needed 
for backwards compatibility. Default is Extended mode. 

5. Static outputs: 

Select whether to support static outputs 

(max 8) or clocked outputs (max 32, depending on DGP 
configuration). Default is Static outputs. 

Menu 4, Factory reset 

Use this menu to set all DGP configurations to default factory 
settings. 

Technical specifications 

Mains power specifications 

Mains Input Voltage (J17 

– AC) 

230 VAC 

10%, 50 Hz 

10%  

Current consumption at 230V~ 

360 mA  

Main board supply voltage 

23 VAC typical 

Power supply specifications 

Power supply voltage 

13.8 VDC 

5% 

Power supply current 

2.9 A max. at 13.8 VDC 

5%   

Auxiliary Power output* (J14) 

13.8 VDC 

5% 

For current see table below 

Battery Power output (J17 

– BAT) 

13.8 VDC 

5%.  

For current see table below 

Battery Type and max. capacity  

Lead acid rechargeable 2 x 
25 Ah 12 V nom. (BS129) 

Main board consumption 

75 mA at 13.8 VDC 

5% 

* Maximum permanent current to power devices external to the control 
equipment in the absence of alarm conditions. 

Available Aux/Battery current based on backup 

 

Time (h)   

Battery capacity (Ah) 

A

pprova

Gra

de

 

D

is

c

har

ge

 

C

har

ge

 

Out

put

 

7.2 

18 

25 

36 

50 

 

 

 

 

Current (mA) 

Incert 

24  24 

Aux 

200 

600 

875 

1200  1200 

 

 

 

Battery 

2525  2125  1850  1525  1525 

EN 1&2 

12  72 

Aux 

490 

1300  1800  1800  1800 

 

 

 

Battery 

2235  1425  925 

925 

925 

EN 3&4 

60  24 

Aux 

40 

220 

330 

500 

550 

 

 

 

Battery 

2685  2500  2395  2225  2175 

NF&A2P 

36  30 

Aux 

110 

360 

550 

850 

1000 



 

 

 

Battery 

2615  2350  2200  1875  1725 

NF&A2P 

72  30 

Aux 

20 

150 

230 

380 

580 



 

 

 

Battery 

2700  2600  2500  2345  2100 

VdS 

30  24 

Aux 

150 

500 

700 

1050  1100 

 

 

Battery 

2575  2225  2025  1675  1625 

VdS 

60  24 

Aux 

40 

220 

330 

500 

550 

 

 

Battery 

2685  2500  2395  2225  2175 

General feature specifications 

End of line resistor 
(standard) 

4.7 k

Ω5% 0.25 W (2.2 kΩ or 10 kΩ) 

Standard on board output  

Ext. siren (J13 

— S+/S−)  

Electronic output 
Rating: 1 A at 13.8 VDC 

Housing dimensions 

ATS1203(N): 370 x 475 x 160 mm 
ATS1204(N): 460 x 475 x 160 mm 

Colour 

Beige 

Operating temperature 

−10 to +55°C (cer5 to 40°C) 

Humidity 

95% noncondensing 

IP protection grade 

IP30 

Fuses 

F4 

Auxiliary 
power & siren 

F2 A, 20x5 

F5 

Battery 

F3 A, 20x5 

[1] 

Mains fuse 

ATS1203: Slow T 

– 400 mA 20x5 

ATS1203NN/ATS1204(N): Fast F

– 630 mA 

20x5 

[1]  Mains fuse is part of the mains terminal block.  

WARNING: 

Before removing the mains fuse, mains power 

must be disconnected! 

Regulatory information 

Manufacturer 

PLACED ON THE MARKET BY: 
UTC Fire & Security Americas Corporation, Inc. 
3211 Progress Drive, Lincolnton, NC, 28092, USA 

AUTHORIZED EU REPRESENTATIVE: 
UTC Fire & Security B.V. 
Kelvinstraat 7, 6003 DH Weert, Netherlands 

Summary of Contents for ATS1203(N)

Page 1: ...Inc 1 24 P N 1064130 ML REV E ISS 01JUL19 ATS1203 N ATS1204 N 8 to 32 Zone DGP with 3A Power Supply Installation Sheet EN DE FR IT 1 2 3 1 2 3 3 4 5 6 1740 ATS1201 1740 ATS CP ATS1210 ATS1116 ATS1203...

Page 2: ...2 24 P N 1064130 ML REV E ISS 01JUL19 4 7 2 7 1 5 4 3 6 8 8 4 5 3 1 2 6...

Page 3: ...x 3 A total Both the mains power supply and the battery are monitored The DGP also provides for 8 to 32 outputs occupying 2 DGP addresses when selected to support more than 16 outputs The ATS1203 N AT...

Page 4: ...l applicable standard Only a qualified electrician or other suitable trained and qualified person should attempt to wire this system to the mains or to the public telephone network Ensure that there i...

Page 5: ...istor must be fitted if external siren not connected 20 Normally closed panel housing tamper contact 21 Normally closed alarm contact 22 External 8 siren speaker or siren Notes If the battery load res...

Page 6: ...e If the battery load test resistor is enabled output 8 follows the battery test except when using clocked output devices Zone numbering The ATS1203 N ATS1204 N has 8 zones that can be expanded using...

Page 7: ...tion at 230V 360 mA Main board supply voltage 23 VAC typical Power supply specifications Power supply voltage 13 8 VDC 5 Power supply current 2 9 A max at 13 8 VDC 5 Auxiliary Power output J14 13 8 VD...

Page 8: ...llen muss der Anschluss an die Stromversorgung mit den lokalen Regelungen bereinstimmen WARNUNG Gefahr von Stromschl gen Entfernen Sie vor der Installation oder Entfernung von Ger ten alle Energiequel...

Page 9: ...er geeigneten Brandschutzklasse HB oder besser entspricht Alle Komponenten die entweder direkt an den Relaiskontakten der Erweiterung oder ber ein externes Relais von den Transistor Schaltausg ngen de...

Page 10: ...werden dass sie die AME Adresse und die AME Adresse 1 abfragt Steckbr cken TERM Abschluss des Datenbusses Wird nur am ersten und letzten Ger t im lokalen Datenbus verwendet 12V 12 V Gleichspannung mi...

Page 11: ...n Die ATS1203 N ATS1204 N k nnen auch 32 Ausg nge unterst tzen Dies k nnen Sie aktivieren indem Sie im Men 3 AME Einstellungen die erste Option 2 AME Adressen Erweiteret AME ausw hlen Denken Sie daran...

Page 12: ...des Batterie Lastwiderstands entsprechen Abbildung 5 Punkt 5 3 Netzpr fung Aktiviert deaktiviert die Netzpr fung Stellen Sie die Pr fung aus wenn keine Netzversorgung verwendet wird um zu verhindern...

Page 13: ...der 2014 35 EU entspricht F r weitere Informationen siehe www utcfireandsecurity com oder www interlogix com 2012 19 EU WEEE Produkte die mit diesem Symbol gekennzeichnet sind d rfen nicht als unsorti...

Page 14: ...s par es Si les entr es de c bles sup rieures ou inf rieures sont utilis es pour passer des c bles utiliser des presses toupes adapt s et conformes la classe de flammabilit HB minimum Le raccordement...

Page 15: ...ouverture normalement ferm 21 Contact d alarme normalement ferm 22 Haut parleur de sir ne externe 8 ohm ou sir ne Notes Si la r sistance de charge batterie est activ e la 4 me sortie de la deuxi me c...

Page 16: ...n choisissant 2 DGP addresses dans le menu 3 DGP settings premi re option du menu avanc 28 vers autres modules Ne pas oublier de faire scruter les 2 DGPs par la centrale Note Lorsque la r sistance de...

Page 17: ...limentation Alimentation secteur principale J17 AC 230 VAC 10 50 Hz 10 Consommation 230V 360 mA Alimentation secondaire de la carte m re 23 VAC nominal Donn es techniques chargeur Tension de sortie au...

Page 18: ...sti possibile utilizzare una connessione fissa oppure una connessione amovibile prelevata da una presa di corrente di rete con messa a terra Se si utilizza un cavo fisso inserire un interruttore bipol...

Page 19: ...sse di infiammabilit Classe HB o superiore Ogni circuito collegato ai contatti dei rel a bordo della centrale o rel esterni o alle uscite elettroniche deve essere a funzionamento in bassa tensione tip...

Page 20: ...deve essere impostata l interrogazione dell indirizzo del DGP E anche l indirizzo successivo 1 Links TERM Terminazione del bus Usare solamente sul primo e ultimo dispositivo sul bus locale 12V Connet...

Page 21: ...Nota Se il test della batteria abilitato l 8 uscita seguir il test batteria tranne se si utilizzano moduli multiplexati Numerazione zone L ATS1203 N ATS1204 N ha 8 zone che possono essere espanse usa...

Page 22: ...azioni di fabbrica Specifiche tecniche Specifiche alimentazione apparato Alimentazione principale J17 AC 230V 10 50 Hz 10 Consumo di corrente a 230 V 360 mA Alimentazione scheda elettronica 23V tipica...

Page 23: ...PER LA PROTEZIONE ANTINCENDIO Per ulteriori informazioni sulle esclusioni di garanzia e sulla sicurezza dei prodotti consultare il sito https firesecurityproducts com policy product warning oppure es...

Page 24: ...24 24 P N 1064130 ML REV E ISS 01JUL19...

Reviews: