P/N 1064130 (ML) • REV E • ISS 01JUL19
7 / 24
Menu 3, DGP settings
Menu 3 provides for some additional settings related directly to
the DGP functionality. Use the MENU key to change the
settings. Use ENTER to accept the settings and move to the
next item.
1. DGP configuration
: selects the number of inputs and
outputs used. Available settings:
•
1 DGP Address: Allows for max 16 inputs/outputs to be
connected. Shows as “DGP: n” where n is the selected
DGP address in menu 1, DGP status (Default setting)
•
1 DGP+exp: Allows for max 32 inputs/16 outputs to be
connected. Shows as “DGP: n + exp” where n is the
selected DGP address in menu 1, DGP status.
•
2 DGP Addresses: Allows for max 32 inputs/outputs to be
connected but requires DGP polling to be enabled for the
DGP address and the DGP a 1. Shows as “DGP:
n + m” where n is the selected DGP address and m is the
a 1 in menu 1, DGP status.
2. Battery load:
Select if the battery load resistor should be
enabled on output 8. It will follow the battery test and add an
additional 68
Ω during the test. This option is required for
regulations (SKAFOR). Default is OFF.
Note:
The setting must correspond with position of the battery
load resistor jumper (Figure 5, item 5).
3. Mains check:
Enable/disable mains check. Set to OFF in
case no mains power supply is used to avoid mains fail being
reported. Default is ON.
4. Extended mode:
To enable anti-mask detection it is
necessary to select Extended mode. Standard mode is needed
for backwards compatibility. Default is Extended mode.
5. Static outputs:
Select whether to support static outputs
(max 8) or clocked outputs (max 32, depending on DGP
configuration). Default is Static outputs.
Menu 4, Factory reset
Use this menu to set all DGP configurations to default factory
settings.
Technical specifications
Mains power specifications
Mains Input Voltage (J17
– AC)
230 VAC
10%, 50 Hz
10%
Current consumption at 230V~
360 mA
Main board supply voltage
23 VAC typical
Power supply specifications
Power supply voltage
13.8 VDC
5%
Power supply current
2.9 A max. at 13.8 VDC
5%
Auxiliary Power output* (J14)
13.8 VDC
5%
For current see table below
Battery Power output (J17
– BAT)
13.8 VDC
5%.
For current see table below
Battery Type and max. capacity
Lead acid rechargeable 2 x
25 Ah 12 V nom. (BS129)
Main board consumption
75 mA at 13.8 VDC
5%
* Maximum permanent current to power devices external to the control
equipment in the absence of alarm conditions.
Available Aux/Battery current based on backup
Time (h)
Battery capacity (Ah)
A
pprova
l
Gra
de
D
is
c
har
ge
C
har
ge
Out
put
7.2
18
25
36
50
Current (mA)
Incert
24 24
Aux
200
600
875
1200 1200
Battery
2525 2125 1850 1525 1525
EN 1&2
12 72
Aux
490
1300 1800 1800 1800
Battery
2235 1425 925
925
925
EN 3&4
60 24
Aux
40
220
330
500
550
Battery
2685 2500 2395 2225 2175
NF&A2P
36 30
Aux
110
360
550
850
1000
Battery
2615 2350 2200 1875 1725
NF&A2P
72 30
Aux
20
150
230
380
580
Battery
2700 2600 2500 2345 2100
VdS
30 24
Aux
150
500
700
1050 1100
B
Battery
2575 2225 2025 1675 1625
VdS
60 24
Aux
40
220
330
500
550
C
Battery
2685 2500 2395 2225 2175
General feature specifications
End of line resistor
(standard)
4.7 k
Ω5% 0.25 W (2.2 kΩ or 10 kΩ)
Standard on board output
Ext. siren (J13
— S+/S−)
Electronic output
Rating: 1 A at 13.8 VDC
Housing dimensions
ATS1203(N): 370 x 475 x 160 mm
ATS1204(N): 460 x 475 x 160 mm
Colour
Beige
Operating temperature
−10 to +55°C (cer5 to 40°C)
Humidity
95% noncondensing
IP protection grade
IP30
Fuses
F4
Auxiliary
power & siren
F2 A, 20x5
F5
Battery
F3 A, 20x5
[1]
Mains fuse
ATS1203: Slow T
– 400 mA 20x5
ATS1203NN/ATS1204(N): Fast F
– 630 mA
20x5
[1] Mains fuse is part of the mains terminal block.
WARNING:
Before removing the mains fuse, mains power
must be disconnected!