16
Advisor Advanced ATSx000A(-IP) Installation and Programming Manual
Figure 16: Dual loop example
(1) Zone terminal
C
Common terminal
Z1 Zone 1 input
Z2 Zone 2 input
(2) Detector
A
Alarm relay
T
Tamper relay
Possible EOL connections are listed in
“EOL connection types” on page 19.
Values for end-of-line resistors
The following list contains the values for end-of-line resistors and possible zone
states. Both the resistance and the voltage measured across the zone are
shown.
Depending on the input type and anti-masking option, the following EOL values
can be available.
Zone state
EOL
Connection
details [1]
Me
as
u
re
[
2]
S
h
o
rt
Ma
sk
ing
No
rmal
Alar
m
F
ault
O
p
en
Single NC
(Item 1)
No EOL
R
(kΩ) —
—
<1
>1
—
—
U (V)
—
—
<3.5
>3.5
—
—
Note:
Values for other EOL are equal to Dual, except all ranges but normal are
alarm ranges.
Single NO
(Item 2)
No EOL
R (kΩ) —
—
>44.70 <44.70
—
—
U (V)
—
—
>11.14 <11.14
—
—
Note:
Values for other EOL are equal to Dual, except all ranges but normal are
alarm ranges.
Dual
10K
(Item 4)
R (kΩ) <3.33
3.33
–
6.67
6.67
–
13.33
13.33
–
26.67
—
>26.67
RA=10
kΩ, RT=5 kΩ,
RF=5
kΩ
U (V)
<5.70
5.70
–
8.10
8.10
–
10.20
10.20
–
11.70
—
>11.70
4K7
(Item 3)
R (kΩ) <1.00
—
1.00
–
6.67
6.67
–
16.84
—
>16.84
RA=4.7
kΩ, RT=4.7 kΩ
U (V)
<2.41
—
2.41
–
8.07
8.07
–
10.74
—
>10.74