5 Parameter Table
- 27 -
Para� No� Para� Name
Setting Range
Unit
Default
Property
A4-25
Increase of pressure loop max�
Output
0 to 50�0
0�1s
2� 0
☆
A4-26
Pressure control PID switching mode
selection
0: original algorithm
1: algorithm 1
2: algorithm 2
3: algorithm 3
1
3
★
A4-33
Integral factor 1 of algorithm 3
0 to 1�00
0�01
0�08
☆
A4-34
Integral factor 2 of algorithm 3
0 to 1�00
0�01
0�08
☆
A4-35
Integral factor 3 of algorithm 3
0 to 1�00
0�01
0�08
☆
A4-36
Integral factor 4 of algorithm 3
0 to 1�00
0�01
0�08
☆
Group F0: Basic Control
F0-00
G/p selection
1: g
2: p
1
1
●
F0-01
Control mode
0: SVC
1: Closed loop vector control
2: V/F
1
1
★
F0-02
Command source selection
0: keypad
1: terminals
2: communication
1
0
☆
F0-03
Main frequency source x selection
0: Digital setting (non-retentive at power down)
1: Digital setting (retentive at power down)
2: AI1
3: AI2
4: AI3
5 to 8: reserved
9: communication
1
0
★
F0-08
Preset frequency
0�00 to F0-10
0�01 Hz
50�00 Hz
☆
F0-09
Running direction
0: same
1: reverse
1
0
★
F0-10
Max� frequency
50�00 to 300�00 Hz
0�01 Hz
200�00 Hz
★
F0-11
Frequency upper limit source
0: F0-12
1: AI1
2: AI2
3: AI3
4: reserve
5: communication
1
0
★
F0-12
Frequency upper limit
F0-14 to F0-10
Hz
200�00
☆
F0-13
Frequency upper limit offset
0�00 to F0-10
Hz
0�00
☆
F0-14
Frequency lower limit
0�00 to F0-12
Hz
0�00
☆
F0-15
Carrier frequency
1 to 8�0
kHz
Model
dependent
☆
F0-16
Carrier frequency auto adjusting
selection
0: Disable
1: enable
1
1
☆
F0-17
Acceleration time 1
0�0s to 6500�0s
0�1s
20�0s
☆
F0-18
Deceleration time 1
0�0s to 6500�0s
0�1s
20�0s
☆