4 Quick Setup
- 20 -
Continued
Para�
Parameter name
Default
Commissioning
Set speed command upper limit
A3-01
Maximum rotational speed
2000
Unit: rpm;
Note
: for hydraulic control mode, A3-01 is seen as 100% speed command, and
now F0-10 has nothing to DO with speed command�
Set pressure command upper
limit
A3-02
System hydraulic pressure
175�0
Unit: kg/cm
2
; range from 0�0 to maximum hydraulic pressure (A3-03)�
Note
: A3-02 is maximum pressure of press machine, for example, 1000ton
press is 265�0 kg/cm
2
�
Also bear in mind A3-02 is seen as 100% pressure command�
Set pressure feedback upper limit
A3-03
Maximum hydraulic pressure
250�0
Unit: kg/cm
2
; range from 0�0 to 500�0 kg/cm
2
�
Note
: A3-03 is maximum pressure of press sensor feedback�
Set DI function
F4-00
DI1 function selection
1
0: no function
1: forward run (FWD)
2: reverse run (REV)
4: forward jog (FJOG)
5: reverse jog (RJOG)
9: fault reset (reset)
11: external fault normally open (NO) input
33: external fault normally closed (NC) input
Setting range: 0 to 59;
F4-01
DI2 function selection
0
Setting range same as DI1;
F4-02
DI3 function selection
0
Setting range same as DI1
F4-03
DI4 function selection
9
Setting range same as DI1�
F4-04
DI5 function selection
0
Setting range same as DI1;
Continued
Para�
Parameter name
Default
Commissioning