4�1 Hydraulic Application Setup Flowchart
Start
Para�
Parameter name
Default
Commissioning
Disable servo drive
Note
: usually if any DI is set as forward or reverse run and the signal is active, then
some operations cannot succeed, such as restoring parameters, changing command
source, which are necessary steps for setup� So it’s seriously recommended to
disable servo drive at the beginning of commissioning�
Restore parameters
FP-01
Parameter operation
0
1
0: no operation
1: restore factory parameters
Note
: usually users have no idea what parameters have been changed, so it’s
seriously recommended to restore parameters to default at the beginning of
commissioning�
Set motor parameters
Motor nameplate
F1-01
Rated motor power
Model dependent
Unit: kW
F1-02
Rated motor voltage
Model dependent
Unit: V
Note
: please follow motor technical specifications to set this parameter, otherwise
motor would probably run with vibration�
F1-03
Rated motor current
Model dependent
Unit: A
F1-04
Rated motor frequency
Model dependent
Unit: Hz
Note
: please follow motor nameplate to set this parameter, otherwise motor auto-
tuning would fail and get E45� Here is the formula for motor frequency:
Frequency = number of motor poles * speed (rpm) / 120�
F1-05
Rated motor speed
Model dependent
Unit: rpm�