5 Parameter Table
- 25 -
Para� No� Para� Name
Setting Range
Unit
Default
Property
A3-26
Pressure command s-curve
deceleration filter time 1
0�001s to 1�000s
0�001s
0�030s
☆
A3-27
Overshoot suppression detection
factor 1
0 to 2000
1
200
☆
A3-28
Overshoot suppression factor 1
0 to 3�000
0�001
0�200
☆
A3-29
Pressure loop gain factor
0�20 to 5�00
0�01
1�00
☆
A3-30
Max� torque during switch from
pressure control to flow control state
50�0% to 250�0%
0�1%
160�0%
☆
A3-31
Pressure command delay time 1
0�000s to 0�500s
0�001s
0�000s
☆
A3-32
Slave drive min� Input
0�0% to A3-34
0�1%
0�0%
☆
A3-33
Slave drive min� Input frequency�
-100�0% to 100�0%
0�1%
0�0%
☆
A3-34
Slave drive mid-point input
A3-32 to A3-36
0�1%
0�0%
☆
A3-35
Slave drive mid-point input
frequency�
-100�0% to 100�0%
0�1%
0�0%
☆
A3-36
Slave drive max� Input
A3-34 to 100�0%
0�1%
100�0%
☆
A3-37
Slave drive max� Input frequency�
-100�0% to 100�0%
0�1%
100�0%
☆
A3-38
Multi-pump host check whether to
enable slave pump
0: slave enable forbidden
1: slave enable permitted
1
0
☆
A3-39
Multi-pump confluence mode
pressure holding gain
20 to 800
1
100
☆
A3-40
Multi-pump injection state acceptable
pressure error during gain decrease
0�0 to 50�0 kg
0�1kg
5�0kg
☆
A3-41
Multi-pump injection state acceptable
min� Flow during gain decrease
0 to 30000 rpm
1 rpm
0 rpm
☆
A3-42
Multi-pump injection state flow
detection time during gain decrease
0�200 to 2�000s
0�001s
0�400s
☆
A3-43
Multi-pump CANLink state pressure
error threshold to Disable slave
pump
0 to 50�0 kg
0�1 kg
5�0 kg
☆
A3-44
Multi-pump CANLink state min. flow
to Disable slave pump
-100�0% to 100�0%
0�1%
0�0%
☆
A3-45
Withdrew speed command slave
pump delays to stop
0�100 to 5�000s
0�001s
1�000s
☆
A3-46
Withdrew speed command slave
pump deceleration time
0�001 to 5�000s
0�001s
0�200s
☆
A3-47
Valve decompression enable delay
0�001 to 5�000s
0�001s
0�100s
☆
A3-48
Valve decompression Disable delay
0�001 to 5�000s
0�001s
0�100s
☆
A3-49
Pressure error lower threshold for
valve decompression enable
0�0 to A3-02 (system pressure)
0�1 kg
0�0 kg
☆
A3-50
Pressure command lower threshold
for valve decompression enable
0�0 to A3-02 (system pressure)
0�1 kg
0�0 kg
☆
A3-51
Current lower threshold for pressure
sensor fault detection
20 to 300%
1%
100%
☆
A3-52
Speed upper threshold for pressure
sensor fault detection
20 to 100%
1%
50�0%
☆
A3-53
Deceleration time of second set high
flow
0�000 to 5�000s
0�001s
0�100s
☆
A3-54
Threshold of second set high flow
0 to 100�0%
0�1%
100�0%
☆