2 Wiring
- 9 -
■
Terminals of Main Control Board
COM DI1 DI2 DI3 DI4 DI5 COM COM DO1
AI2 AI3 GND +10V +15V GND AO1 AO2 GND
T/A1 T/B1 T/C1
AI3 input jumper, voltage input as default
J5
J6
J4
I
V
AO1 output jumper, voltage output as default
AO2 output jumper, voltage output as default
AI1
T/A2 T/C2
J1
DI power supply source jumper(internal/external), internal as
default
2
Terminal
Terminal name
Description
+10V-GND
+10 VDC power supply
Internal 10 VDC power supply
+15V-GND
+15 VDC power supply
Internal 15 VDC power supply can be used for pressure sensor
Max� Output current: 10 mA
AI1-GND
Analog input 1
1� Input voltage range: 0 to 10 VDC
2. Input impedance: 22 kΩ
AI2-GND
Analog input 2
AI3-GND
Analog input 3
1� Input voltage range: 0 to 10 VDC/0 to 20 mA, selected by J5 jumper
2. Input impedance: 22 kΩ (voltage input), 500 Ω (current input)
DI1- COM
Digital input 1
1� Optically-coupled isolation compatible with dual-polarity inputs, input frequency less than
100 Hz
2� Power supply source determined by jumper J1
3. Input impedance: 1.39 kΩ
4� Voltage range for inputs: 9 to 30 V
DI2- COM
Digital input 2
DI3- COM
Digital input 3
DI4- COM
Digital input 4
DI5- COM
Digital input 5
AO1-GND
Analogue output 1
1� Either a voltage or a current output, Determined by jumper J4�
2. Max. Load resistance: 500 Ω
3� Output voltage range: 0 to 10 V
4� Output current range: 0 to 20 mA�
AO2-GND
Analogue output 1
1� Either a voltage or a current output, determined by jumper J6�
2. Max. Load resistance: 500 Ω
3� Output voltage range: 0 to 10 V
4� Output current range: 0 to 20 mA�