AC-SVX002C-EN
59
N
No
otte
ess::
•
Tracer
®
TU is designed and validated for
this minimum laptop configuration. Any
variation from this configuration may have
different results. Therefore, support for
Tracer TU is limited to only those laptops
with the configuration previously specified.
•
For more information, see TTU-SVN01*-EN
Tracer
®
TU Getting Started Guide
Figure 45.
Tracer TU
Integrated Rapid Restart
Chiller controls are designed and engineered for Rapid
Restart
™
. In the event of a power interruption, the
chiller will start a compressor before the front panel
display is fully powered up, eliminating the need for an
uninterrupted power supply (UPS). Advanced features
and functionality are built into the chillers. Bringing a
chiller back online rapidly after a loss of power is
critical to operations in mission critical environments,
which demand the highest levels of reliability.
Under optimal conditions, it can restart in as little as 45
seconds with no need for uninterrupted power supply
(UPS). An 80 percent cooling load can be achieved in
less than 2.5 minutes after power restoration.