AC-SVX002C-EN
83
Table 33.
Communication diagnostics (continued)
Diagnostic
Name
Affects
Target
Severity
Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level
Comm Loss:
Percent
Capacity
Output
Chiller
Warning
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
External Ckt
Lockout
Circuit
Special Mode
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 30 second
period. MP will nonvolatily hold the lockout state
(enabled or disabled) that was in effect at the time of
comm loss.
Remote
Comm Loss:
External Hot
Water
Command
Chiller
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Reversing
Valve
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Shared V Coil
Isolating Valve
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Supplemental
Heater Relay X
Chiller
Warning
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Liquid Line
Temperature
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Liquid Line
Pressure
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Dynamic
Receiver Fill
Valve
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Hot Gas Bypass
Valve
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Sump Heater
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
SLHX Valve
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
SLHX Entering
Temperature
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote