AC-SVX002C-EN
81
Table 33.
Communication diagnostics (continued)
Diagnostic
Name
Affects
Target
Severity
Persistence
Active
Modes
[Inactive
Modes]
Criteria
Reset
Level
Comm Loss:
High Pressure
Cutout Switch
Circuit
Immediate
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Evaporator
Water Flow
Switch
Chiller
Immediate
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Local BAS
Interface
Chiller
Warning and
Special Action
NonLatch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period. Use the last values sent from BAS.
Remote
Comm Loss:
Compressor
Fault Input
Cprsr
Immediate
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Run Command
Compressor X
Cprsr
Immediate
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Fan Board 1
Relay X
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Fan Board 2
Relay X
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Comm Loss:
Fan Speed
Select Board
Relay X
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Condenser Fan
Enable, Shared
Circuit 1&2
Circuit
Warning
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Condenser Fan
Enable
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Fan Inverter
Speed
Command
Circuit
Normal
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Fan Inverter
Speed
Command
Shared,
Shared Circuit
1&2
Circuit
Warning
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Programmable
Relay Board 1
Chiller
Warning
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Programmable
Relay Board 2
Chiller
Warning
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote
Comm Loss:
Evaporator
Antifreeze
Heater
Chiller
Warning and
Special Action
Latch
All
Continual loss of communication between the MP and
the Functional ID has occurred for a 35-40 second
period.
Remote