71
VALUE OPTION
DESCRIPTION
10
Error local – NO
The contact is closed as soon as an error occurs in the unit
in question.
11
Fan active – NO
The contact is closed when the fans are running.
13
Heating on
The contact is closed when the unit requires heating. Use
this to switch the heating system ON or OFF via the unit.
15
Risk of freezing
The contact is closed when the temperature inside the unit
drops below 7 °C.
17
Use boost function
The contact is closed when the difference between the
desired temperature and the room temperature is greater
than the value set for 33. Boost function.
31
Copy input 1
The output follows the contact on input 1
32
Copy input 2
The output follows the contact on input 2
33
Copy input 3
The output follows the contact on input 3
40
Overheating
protection
The contact is opened as soon as the high-limit thermostat
has been activated (only for output 3, only for models with
electrical heating)
41
Fan malfunction – NC The contact is opened when there is a malfunction in the
fan. (only for output 3, only for types L and XL)
51
Error – NC
The contact is opened as soon as an error occurs.
52
Dirty filter – NC
The contact is opened as soon as the maximum filter
lifespan has expired.
60
Error local – NC
The contact is opened as soon as an error occurs in the
unit in question.
61
Fan active – NC
The contact is opened when the fans are running.
71.
Indoor temperature sensor
Select the sensor which the system must use for the
indoor temperature:
Select the sensor on the unit if no room
sensor has been installed.
Select the room sensor if it has been installed.
Select the average between the unit sensor
and the room sensor.
It is possible to limit the room temperature that can
be set by the user. Set a minimum and a maximum
room temperature.